"Blackboard light":
Additional illumination can be switched on and off separately. E.g. illumination for a
blackboard in school classrooms. The additional illumination also switches off
automatically together with the ceiling lights.
The additional lighting is operated with a separate push-button connected via the
6494-500 Extension unit connection.
The additional switching output must be configured as a panel light through the app.
"Manual":
The additional switch contact (actuator 2) is switched only manually via the app. There
is no dependence to actuator 1 (e.g. DALI output).
"HVAC":
The "HVAC" operation mode (heating, air conditioning and ventilation) enables a purely
presence-dependent switching of the additional switch contact (actuator 2). The ambient
brightness is not taken into consideration here.
This function, for example, is used to control a fan motor in WC facilities.
Extension unit operation
An additional operation for on/off switching via a push-button:
For Monoblock devices on extension unit input 1C of the presence detector.
For ABB flexTronics
mounted insert used.
A manual change of the current switching state can be implemented. The return to
automatic mode and/or previously selected operation mode takes place after the room is
left plus the set switch-off delay.
The lighting is also switched on in semi-automatic mode through the operation of this
extension.
Continuous ON
The lighting is switched on. For devices with infrared remote control, the duration amounts
to 8 hours. For devices with Bluetooth function, the duration is freely selectable through the
smartphone app "ABB Watchdog Remote control".
To activate this function, press the corresponding button on the IR service remote control
6843.
A renewed press of the button on the remote control deactivates the continuous light ON
function.
Only Monoblock devices:
For the activation of this function, a push-button is connected to channel 1 of the 6494-
500 Extension unit connection. In the case of the DALI main unit, the "Continuous Light"
function must be activated via the extension push-button.
The return to automatic mode and/or previously selected operation mode is
implemented through one of the following possibilities:
Push-button/extension operation (directly connected to the extension input 1C of the
presence detector).
Simultaneous actuation of the push-buttons for "Continuous ON" and "Continuous
OFF".
Via app.
Automatic after the expiration of the "Continuous ON" time.
This function cannot be combined with the panel light.