DE FAU LT DATA M AP
Modbus
Function
Code
2
2
2
2
2
2
2
2
2
2
2
2
Continued on the next page
46
Modbus
Device
Register
Number
11001
1
11002
1
11003
1
11004
1
11005
1
11006
1
11007
1
11008
1
11009
1
11010
1
11011
1
11012
1
Description
Stopped
Runs
CW or K1
CCW or K2
Ready
Alarm
New Trip
Test
HW local
Bus local
Remote
DI0
DATA M A P PI NG
Remarks
1 = Motor Stopped or
Tripped or Feeder
open
1 = Motor Runs or
Feeder closed
1 = Motor Runs Clock-
wise
1 = Motor Runs Coun-
ter Clockwise
1 = Off and Ready for
Operation. No
alarm/trip is available
1 = Any Alarm condi-
tion of protection or
supervision functions.
1 = Any Trip condition
of the protection or
supervision functions
1 = Main switch set to
test position. (Motor
cannot start)
1 = Control Access is
selected to hardwired
I/O from Local / Re-
mote input on M10x-M
1 = Control Access is
passed to any control
station on the switch-
gear control network.
1=Control Access is
passed to the Process
Control System
1= Digital Input 0 of
M10x-M is on
1TG C 9 0 8 0 0 4 M 0 2 0 1