b) Configuration with fireplace comburent air inlet communicating with the installation room, with fan hot air outlets and natural
convection outlets not connected.
The fireplace can function by taking the comburent air from the installation room, connecting it with the extensible aluminium pipe (Ø120 mm
and maximum length 100 cm) to the coating (1). In this configuration it is mandatory to make an opening in the installation room (minimum
Ø200 mm) (2), communicating with the outside, guaranteeing a proper intake of comburent air such that it does not depressurise the
installation room.
In this configuration, the connection between the fireplace comburent air inlet to the coating and the installation room opening
are mandatory.
Make an opening (minimum 600 cm
) in the coating top part (2) to allow hot air exit (of the corresponding outlets located on the fireplace (4))
2
and an opening (minimum 600 cm
) in the coating lower part (5) for the heating air intake from the installation room.
2
The four hot air outlets on the fireplace (4) may be let as not connected as such hot hair is conveyed in the installation room through an
opening of the coating top part.
In case of hot air outlet canalisation to the nozzles, use an extensible aluminium pipe Ø120 mm.
The coating top and lower parts openings are mandatory.