Njoy Garun 30KL User Manual page 14

3 phase in / 3 phase out ups
Hide thumbs Also See for Garun 30KL:
Table of Contents

Advertisement

H: High voltage point for ECO mode. The setting range is from "Rated
output voltage + 5V" to "Rated output voltage + 11V". "Rated output voltage
+ 5V" is default setting.
ECO FREE Range: Set the ECO frequency range. The setting range is from
46Hz to 54Hz when the UPS is 50Hz system and from 56Hz to 64Hz when
the UPS is 60Hz system.
• BATTERY
Battery setting page
Battery Warning Voltage:
HIGH: High battery warning voltage. The setting range is 14.0V ~ 15.0V.
14.4V is default setting.
LOW: Low battery warning voltage. The setting range is 10.1V ~ 14.0V.
11.4V is default setting. This parameter setting is related to "Shutdown
Voltage" setting. This setting value should be higher than "Shutdown Voltage"
setting.
Shutdown Voltage: If battery voltage is lower than this point in battery mode,
UPS will automatically shut down. The setting range is 10.0V ~ 12.0V.
10.7V is default setting. (The setting is only available for long-run model)
BATT Age: Set up battery age.
Battery Parameter:
Battery AH: setting battery capacity.
26
• MISCELLANEOUS
Miscellaneous setting page
Auto Restart: (This function is reserved for future use)
Enable: After "Enable" is set, once UPS shutdown occurs due to low
battery and then utility restores, the UPS will return to line mode.
Disable: After "Disable" is set, once UPS shutdown occurs and the utility
restores, the UPS will not automatically turn on
Shutdown Delay Min: UPS will shut down in setting minutes. The countdown
will start after confirming the pop-up screen.
Restore Delay Min: UPS will automatically restart in setting minutes after the
UPS shuts down.
New Password: Set up new password to enter "ADVANCE ► User" menu.
27