General
General Setting page 1
Date/Time: Set the date and time. The format is YYYY-MM-DD HH:MM:SS.
The calendar day will be automatically changed when the year, month and
date are set.
Language: Set the LCD language.
Input Source: Select the input source. There are two options: Line (utility)
and generator. Line is default setting. This setting value will show on the main
page. When "generator" is selected, the acceptable input frequency will be
fixed at the range of 40~70Hz. This setting value will show on the status bar.
Service Contact: Set the name of contact person and the maximum length is
18 characters.
Service Phone: Set the service phone number. Only 0~9, + and – are
accepted. The maximum length is 14 characters.
Service Mail: Set the service email accounts up to two and the maximum
length is 36 characters.
General Setting page 2
22
Audio Alarm: There are two events available to mute. You may choose
"Enable" or "Disable" alarm when related events occur.
Enable: When selected, alarm will be mute when related events occur.
Disable: When selected, UPS will alarm when related events occur.
All Mute: When "enable" is selected, all the faults and warnings will be mute.
It will show
icon on the top right corner of the main screen.
Mode Mute: UPS status mode alarm enable/disable. If "Mode Mute" is
activated, it will show
icon on the top right corner of the main screen.
Advance
Advance Password Page
It's required to enter password (4 digits) to access to the "ADVANCE" page.
Advance - User
To access "Advance-User" settings menu page, the default password is
"0000". If entered password is right, the page will jump to setting screen. If
the password is wrong, it will ask to enter again.
Password error page