Advance Setting Menu Page
There are three sub-menus under "Advance ► User" setting: ELECTRONIC,
BATTERY and MISCELLANEOUS.
• ELECTRONIC
Electronic Menu Page 1
Output Voltage: Select the output rated voltage. There are four options,
208V, 220V, 230V and 240V.
Output Frequency: Select output rated frequency.
50Hz: The output frequency is setting for 50Hz.
60Hz: The output frequency is setting for 60Hz.
CVCF Mode (constant voltage and constant frequency function)
Enable: CVCF function is enabled. The output frequency will be fixed at
50Hz or 60Hz according to setting of "OP Freq.". The input frequency could
be from 46Hz to 64Hz.
24
Disable: CVCF function is disabled. The output frequency will synchronize
with the bypass frequency within 46~54 Hz for 50Hz system or within
56~64 Hz for 60Hz system. Disable is the default setting.
Bypass Forbid:
Enable: Bypass forbid is enabled. When selected, it's not allowed for
running in Bypass mode under any situations.
Disable: Bypass forbid is disabled. When selected, UPS will run in Bypass
mode depending on "Bypass at UPS off" setting. It is the default setting.
Electronic Menu Page 2
Bypass at UPS off: Select the bypass status when manually turning off the
UPS. This setting is only available when "Bypass forbid." is set to "Disable".
Enable: Bypass enabled. When selected, bypass mode is activated.
Disable: Bypass disabled. When selected, no output through bypass when
manually turning off the UPS.
Bypass Voltage Range: Set the bypass voltage range.
L: Low voltage point for bypass. The setting range is 176V ~ 209V.
H: High voltage point for bypass. The setting range is 231V ~ 264V.
Bypass FREE Range: Set the bypass frequency range.
The acceptable bypass frequency range from 46Hz to 54Hz when UPS is
50Hz system and from 56Hz to 64Hz when UPS is 60Hz system.
ECO mode: Enable/Disable ECO mode. Default setting is "Disable".
ECO Voltage Range: Set the ECO voltage range.
L: Low voltage point for ECO mode. The setting range is from "Rated
output voltage – 5V" to "Rated output voltage - 11V". "Rated output voltage
– 5V" is default setting.