Carrier 40MPHA Service Manual

Carrier 40MPHA Service Manual

High wall unit ductless system
Hide thumbs Also See for 40MPHA:

Advertisement

40MPHA
High Wall Unit Ductless System
Sizes 09 to 24

TABLE OF CONTENTS

SAFETY CONSIDERATIONS ....................................................... 1
INTRODUCTION............................................................................ 1
MODEL NUMBER NOMENCLATURE ....................................... 2
SPECIFICATIONS .......................................................................... 3
DIMENSIONS ................................................................................. 4
CLEARANCES................................................................................ 6
ELECTRICAL DATA ..................................................................... 7
WIRING ........................................................................................... 7
CONNECTION DIAGRAM............................................................ 8
WIRING DIAGRAM....................................................................... 9
FAN AND MOTOR SPECIFICATIONS ........................................ 11
REFRIGERATION CYCLE DIAGRAM........................................ 11
REFRIGERANT LINES .................................................................. 12
SYSTEM EVACUATION AND CHARGING ............................... 12
OPERATION MODES AND FUNCTIONS ................................... 13
ROR CODE...................................................................................... 20
QUICK MAINTENANCE BY ERROR CODE .............................. 24
TROUBLESHOOTING BY ERROR CODE .................................. 25
DIAGNOSIS AND SOLUTION...................................................... 27
DISASSEMBLY INSTRUCTIONS ................................................ 40
APPENDICES.................................................................................. 64

SAFETY CONSIDERATIONS

Installing, starting up, and servicing air-conditioning equipment can
be hazardous due to system pressures, electrical components, and
equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics should install,
start-up, and service this equipment.
Untrained personnel can perform basic maintenance functions such as
cleaning coils. All other operations should be performed by trained
service personnel.
When working on the equipment, observe the precautions in the
literature and on tags, stickers, and labels attached to the equipment.
Follow all safety codes. Wear safety glasses and work gloves. Keep a
quenching cloth and fire extinguisher nearby when brazing. Use care
in handling, rigging, and setting bulky equipment.
Read this manual thoroughly and follow all the warnings or cautions
included in literature and attached to the unit. Consult local building
codes and National Electrical Code (NEC) for special requirements.
Recognize safety information. This is the safety-alert symbol
When you see this symbol on the unit and in instructions or manuals,
be alert to the potential for personal injury. Understand these signal
words: DANGER, WARNING, and CAUTION.
Service Manual
These words are used with the safety-alert symbol. DANGER
identifies the most serious hazards which will result in severe personal
PAGE
injury or death. WARNING signifies hazards which could result in
personal injury or death. CAUTION is used to identify unsafe
practices which may result in minor personal injury or product and
property damage. NOTE is used to highlight suggestions which will
result in enhanced installation, reliability, or operation.

INTRODUCTION

.
This service manual provides the necessary information to service,
repair, and maintain the indoor units. This manual has an appendix
with data required to perform troubleshooting. Use the Table of
Contents to locate a desired topic.
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing the system, the main
electrical disconnect switch must be in the OFF position. There may
be more than 1 disconnect switch. Lock out and tag switch with a
suitable warning label.
WARNING
EXPLOSION HAZARD
Failure to follow this warning could
result in death, serious personal injury,
and/or property damage.
Never use air or gases containing oxygen
for leak testing or operating refrigerant
compressors. Pressurized mixtures of air
or gases containing oxygen can lead to
an explosion.
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or
improper operation.
Do not bury more than 36 in. (914 mm) of refrigerant pipe in the
ground. If any section of pipe is buried, there must be a 6 in. (152 mm)
vertical rise to the valve connections on the outdoor units. If more
than the recommended length is buried, refrigerant may migrate to the
cooler buried section during extended periods of system shutdown.
This causes refrigerant slugging and could possibly damage the
compressor at start-up.

Advertisement

Table of Contents
loading

Summary of Contents for Carrier 40MPHA

  • Page 1: Table Of Contents

    40MPHA High Wall Unit Ductless System Sizes 09 to 24 Service Manual TABLE OF CONTENTS These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal PAGE injury or death. WARNING signifies hazards which could result in personal injury or death.
  • Page 2: Model Number Nomenclature

    Sequential Serial Number Year of Manufacture V = ALL MODELS Use of the AHRI Certified TM Mark indicates a manufacturer’s participation in the program For verification of certification for individual products, go to www.ahridirectory.org. Specifications subject to change without notice. 40MPHA-03SM...
  • Page 3: Specifications

    5.0 (2.39) (L/h) Field Drain Pipe Size O.D. in (mm) 1 (25.4) 1 (25.4) 1 (25.4) 1 (25.4) *Performance may vary based on the compatible outdoor units. See respective pages for performance data. 40MPHA-03SM Specifications subject to change without notice.
  • Page 4: Dimensions

    Fig. 1 — Sizes 9K and 12K NOTE: Drain adapter included with the indoor unit to allow the use of a 3/4 in. PVC Schedule 40 pipe where the actual outside diameter is 1.05 in. Specifications subject to change without notice. 40MPHA-03SM...
  • Page 5 14.25 (362) Width In. (mm) 49.57 (1259) 49.57 (1259) Depth In. (mm) 11.10 (282) 11.10 (282) Weight-Net Lbs (kg) 43.4 (19.7) 43.4 (19.7) Piping Drain Hose Fig. 2 — Sizes 18K and 24K 40MPHA-03SM Specifications subject to change without notice.
  • Page 6: Clearances

    NOTE: The top clearance recommended for proper return airflow is 5.9 in (15cm). Reduction of this clearance may decrease the performance of these units. This may be reduced to 3.2 in (80mm) as long as the right and left clearances are achieved. Specifications subject to change without notice. 40MPHA-03SM...
  • Page 7: Electrical Data

    Disconnecting means must be provided and shall be located within sight and readily accessible from the air conditioner. Connecting cable with conduit shall be routed through the hole in the conduit panel. 40MPHA-03SM Specifications subject to change without notice.
  • Page 8: Connection Diagram

    1. Do not use thermostat wire for any connection between the indoor and outdoor units. 2. All connections between the indoor and outdoor units must be as shown in Figure 4. The connections are polarity sensitive and improper wiring will result in a fault code. Specifications subject to change without notice. 40MPHA-03SM...
  • Page 9: Wiring Diagram

    Output: DC 5V To CCM Comm.Bus or 485 Wire-controller CN 40 Input: DC 5V Connect to display board CN 43 Input: DC 12V Connect to main board CN 46 Output: DC 5V To Remote Switch 40MPHA-03SM Specifications subject to change without notice.
  • Page 10 Output:5VDC Humidity sensor CN 4 Output:12VDC Room temperature sensor (optional) MULTI-FUNCTION CONTROL BOARD CN42&CN41 Output:5VDC To CCM Comm. Bus or 485 Wire-controller CN40 Input:5VDC Connect to display board CN 46 Output:5VDC To Remote Switch Specifications subject to change without notice. 40MPHA-03SM...
  • Page 11: Fan And Motor Specifications

    WAY VALVE CAPILLARY TUBE HEAT HEAT EXCHANGE EXCHANGE (EVAPORATOR) (CONDENSER) T1 Room temp. sensor T2 Evaporator temp. sensor GAS SIDE WAY VALVE WAY VALVE ACCUMULATOR COOLING COMPRESSOR HEATING Fig. 7 — Heat Pumps 40MPHA-03SM Specifications subject to change without notice.
  • Page 12: Refrigerant Lines

    Ensure tubes are not rubbing against each other or any sheet metal. Pay close attention to feeder tubes, making sure wire ties on feeder tubes are secure and tight. Gas side valve Fig. 9 — Manifold Specifications subject to change without notice. 40MPHA-03SM...
  • Page 13: Operation Modes And Functions

    • If one temperature sensor malfunctions, the air conditioner continues operation and displays the corresponding error code, allowing for emergency use. • When more than one temperature sensor malfunctions, the air conditioner ceases operation. 40MPHA-03SM Specifications subject to change without notice.
  • Page 14 T4 is more than 59°F (15°C) or no T4 or T4 fault. • Change setting temperature • Turbo or sleep function on/off • Various frequency limit shutdown occurs NOTE: CDIFTEMP is EEPROM setting parameter. It is ° ° F (2 Specifications subject to change without notice. 40MPHA-03SM...
  • Page 15 • When T1-Tsc is lower than or equal to -1.5°F (-3°C), fan speed increases to 100%. Outdoor Fan Control •The outdoor unit runs at a different fan speed according to T4 and compressor running frequency. • For different outdoor units, the fan speeds differ. 40MPHA-03SM Specifications subject to change without notice.
  • Page 16 • The operating time for the SLEEP mode is 8 hours, after which, the unit exits this mode and turns off. • The timer setting is available in this mode. Specifications subject to change without notice. 40MPHA-03SM...
  • Page 17 Outdoor fan speed EXV opening angle EXV opening angle Indoor fan speed Indoor fan speed Indoor humidity Adjusted setting temperature Indoor dust concentrations N/A - Not available WIFI signal strength GA algorithm frequency 40MPHA-03SM Specifications subject to change without notice.
  • Page 18 For other models, please connect discharge resistance (approximately 100Ù 40W) or a soldering iron (plug) between the +, - terminals of the electrolytic capacitor on the other side of the outdoor PCB. Fig. 14 — Discharge Position NOTE: Fig. 14 is for reference only. Actual appearances may vary. Specifications subject to change without notice. 40MPHA-03SM...
  • Page 19 Test the indoor unit using the remote control. If the unit display is working however will not respond to the remote, the indoor PCB needs to be replaced. If there is no display after pressing LED and the unit responds, the display board needs to be replaced. 40MPHA-03SM Specifications subject to change without notice.
  • Page 20: Error Diagnosis And Troubleshooting Without Error Code

    ERROR DIAGNOSIS AND TROUBLESHOOTING WITHOUT ERROR CODE WARNING UNIT DAMAGE HAZARD Be sure to turn off unit before any maintenance to prevent damage or injury. Table 11 — Remote Maintenance Remote Electrical Circuit Refrigerant Circuit Others Maintenance The setting The ambient Interference temp is SILENCE...
  • Page 21 ERROR DIAGNOSIS AND TROUBLESHOOTING WITHOUT ERROR CODE (continued) Table 12 — Field Maintenance Field Electrical Circuit Maintenance Faulty Faulty Possible Wrong setting Faulty Shorted or Shorted or Blown fuse Loose Shorted or Safety device thermostat/ Faulty Shorted or magnetic Faulty causes Power failure place of temp...
  • Page 22 ERROR DIAGNOSIS AND TROUBLESHOOTING WITHOUT ERROR CODE (continued) Table 13 — Field Maintenance Field Maintenance Refrigerant Circuit Insufficient Air or non- Expansion Leaking Dirty or Short Broken Power Dirty condensible High temp. Insufficient Expansion valve or power Possible causes Compressor Refrigerant Restricted Refrigerant...
  • Page 23 ERROR DIAGNOSIS AND TROUBLESHOOTING WITHOUT ERROR CODE (continued) Table 14 — Field Maintenance Field Maintenance Others Possible causes Contact of piping with other piping or Heavy load condition Loosen hold down bolts and/or screws Shipping plates remain attached Poor choices of capacity of trouble external plate Unit will not start...
  • Page 24: Quick Maintenance By Error Code

    Outdoor PCB Display Board  Reactor Indoor fan motor  Outdoor fan motor    Temperature sensor T2 Sensor Additional refrigerant   Compressor    IPM board Outdoor unit Occupancy Sensor Specifications subject to change without notice. 40MPHA-03SM...
  • Page 25: Troubleshooting By Error Code

    Measure the resistance value of each winding by using the tester. Fig. 15 — Compressor Checking Table 17 — Compressor Checking POSITION RESISTANCE VALUE ATM115D43UFZ2 Blue - Red  Blue - Black 1.87 (20°C/68°FX) Red - Blue 40MPHA-03SM Specifications subject to change without notice.
  • Page 26 Table 18 — IPM Continuity Check Normal Resistance Normal Resistance Digital Tester Digital Tester Value Value (+) Red (-) Black (+) Red (-) Black ∞ ∞   (Several M  (Several M  (+) Red Specifications subject to change without notice. 40MPHA-03SM...
  • Page 27: Diagnosis And Solution

    PCB . Remarks: The location of the EEPROM chip on the indoor and outdoor PCB is shown in Figures 16 and 17: Fig. 17 —EEPROM Chip (Outdoor Unit) Fig. 16 —EEPROM Chip (Indoor Unit) 40MPHA-03SM Specifications subject to change without notice.
  • Page 28 Power on. Check the reactor. Is the error resolved? Replace the Is it normal? reactor. Replace the outdoor PCB. Replace the outdoor PCB. Power on. Is the error resolved? Replace the indoor PCB. Specifications subject to change without notice. 40MPHA-03SM...
  • Page 29 • Use a multimeter to test the reactor resistance that does not connect with the capacitor. • The normal value should be around zero ohm otherwise the reactor is malfunctioning. Fig. 19 — Multimeter 40MPHA-03SM Specifications subject to change without notice.
  • Page 30 Troubleshooting and repair: Check the connections and power supply. Correct the connections. Power on the Is it normal? unit when the power supply is good. Indoor main PCB is defective. Replace the indoor main PCB. Specifications subject to change without notice. 40MPHA-03SM...
  • Page 31 Check the fan motor wiring. Is it improperly wired ? Ensure proper connections. Measure the voltage for the fan motor from the PCB. Is it within normal parameters? Replace the indoor /outdoor PCB. Replace the fan motor. 40MPHA-03SM Specifications subject to change without notice.
  • Page 32 If the value of the voltage is less than 100V(208~240V power supply) or 50V(115V power supply), the PCB must has problems and needs to be replaced. Fig. 22 — Indoor AC Fan Motor Specifications subject to change without notice. 40MPHA-03SM...
  • Page 33 Wait 2 minutes then restart. Is the unit still displaying an error code? The unit is operating as designed. Check the Occupancy Sensor module wiring. Is it good? Ensure proper connections. Replace the Occupancy Sensor module. 40MPHA-03SM Specifications subject to change without notice.
  • Page 34 DC 310V, 340V or 380V? On unit start up Replace the IPM board. is the unit in the 220V~400 range? Check the reactor. Is it in working order? Replace outdoor PCB. Replace the reactor. Specifications subject to change without notice. 40MPHA-03SM...
  • Page 35 Faulty PCB • Connection problems Troubleshooting and Repair: Check the fastening screws on the PCB and IPM radiator. Replace the outdoor Are they fixed tightly? control PCB. Tighten the screws and apply silicon grease. 40MPHA-03SM Specifications subject to change without notice.
  • Page 36 Please refer to “Fan Speed Is it functioning properly? Malfunction” solution. Check the compressor resistance values. Are they within Replace the compressor. acceptable parameters ? Replace the outdoor PCB. Specifications subject to change without notice. 40MPHA-03SM...
  • Page 37 PCB. Is it properly wired ? Ensure proper connections . Measure the resistance value of the sensor. Is it within acceptable Replace the sensor. parameters? Replace indoor or outdoor PCB. Fig. 23 —Multimeter 40MPHA-03SM Specifications subject to change without notice.
  • Page 38 Check the wirings and connection. Correct the connection Is it normal ? or replace the wirings. Replace the indoor main PCB. Is the problem solved? Replace the display board. The unit operates normally. Specifications subject to change without notice. 40MPHA-03SM...
  • Page 39 Check the connections and wires. Ensure proper connections or Are they properly connected? replace the wires. Check the reactor. Is it in working order? Replace the outdoor PCB. Replace the outdoor unit. 40MPHA-03SM Specifications subject to change without notice.
  • Page 40 Check the outdoor fan and the outdoor unit ventilation. Refer to the “Fan Speed is Out of Control” Is it in working order? solution. Check the compressor resistance values. Replace the compressor. acceptable parameters? Replace the outdoor PCB. Specifications subject to change without notice. 40MPHA-03SM...
  • Page 41: Disassembly Instructions

    1) Hold the front panel by the tabs on Front Panel both sides and lift it. 2) Push up the bottom of the air filter while pressing the buttom of the unit, and then pull the air filter out (downwards). Filter 40MPHA-03SM Specifications subject to change without notice.
  • Page 42 3) Open the horizontal louver and push the hook towards the right to open. Horizontal Louver Hook 4) Bend the horizontal louver lightly with both hands to loosen the hooks, then remove the horizontal louver. Hook Specifications subject to change without notice. 40MPHA-03SM...
  • Page 43 6) Disconnect the two connectors on the display board. 7) Slide the front panel side to side to release each axis. 8) Remove the screw (1) and rotate the display board clockwise. Next, remove the clips. 40MPHA-03SM Specifications subject to change without notice.
  • Page 44 Next, remove the electronic box cover and the terminal cover along the direction indicated in the image (on the right side) to remove it. 4) Disconnect the fan motor connector and the step motor. Specifications subject to change without notice. 40MPHA-03SM...
  • Page 45 Main Board Electronic Box Pipe Temperature Sensor 7) Each port connector is indicated in the image to the right. Terminals Ground Wire Indoor Fan Motor Display Board Swing Motor 40MPHA-03SM Specifications subject to change without notice.
  • Page 46 Pipe Holder 2) Remove the screws (3) on the evaporator located on the fixed plate. Screws 3) Remove the screws (2) on the evaporator located at the base of the bearing side. Screws Specifications subject to change without notice. 40MPHA-03SM...
  • Page 47 Indoor Unit Sizes 09K-12K (Evaporator) (continued) l l I 4) Remove the screw (1) on the evaporator located at the top of the evaporator. Evaporator 5) Remove the evaporator. 40MPHA-03SM Specifications subject to change without notice.
  • Page 48 1) Remove the screws (2) and remove the fixing board of the fan motor. Screws 2) Remove the bearing sleeve. Specifications subject to change without notice. 40MPHA-03SM...
  • Page 49 NOTE: Remove the front panel and electrical parts (refer to the front panel, electrical parts removal steps) before disassembling the step motor. l l I 1) Remove the screws (2), then remove the stepping motor. Stepping Motor 40MPHA-03SM Specifications subject to change without notice.
  • Page 50 NOTE: Remove the front panel and electrical parts (refer to the front panel, electrical parts, evaporator and fan motor and fan removal steps) before disassembling the occupancy sensor. l l I 1) Remove the screw (1), then remove the Occupancy Sensor. Occupancy Sensor Specifications subject to change without notice. 40MPHA-03SM...
  • Page 51 I 1) Hold the front panel by the tabs on Front Panel both sides and lift it. 2) Push up the bottom of the air filter (step 1), then pull it out downwards. 40MPHA-03SM Specifications subject to change without notice.
  • Page 52 3) Open the horizontal louver and push the hook towards the left to open it. Horizontal Louver Hook 4) Bend the horizontal louver lightly with both hands to loosen the hooks, then remove the horizontal louver. Hook Specifications subject to change without notice. 40MPHA-03SM...
  • Page 53 Indoor Unit Sizes 18K-24K (Front Panel) (continued) l l I 5) Pry the electrical cover with a screwdriver and rotate it towards the left, then remove it. 6) Disconnect the connector on the display board. 40MPHA-03SM Specifications subject to change without notice.
  • Page 54 Indoor Unit Sizes 18K-24K (Front Panel) (continued) l l I 7) Slide the front panel side to side to release each axis. 8) Open the screw cap and then remove the screws (3). Specifications subject to change without notice. 40MPHA-03SM...
  • Page 55 9) Release the hooks by hand. 10) Release the 5 hooks in the back. 11) Pull out the panel frame, while pushing the hook through the clearance between the panel frame and the heat exchanger. 40MPHA-03SM Specifications subject to change without notice.
  • Page 56 13) Remove the display board’s screw (1). 14) Rotate the display board in the direction shown in the picture (on the right). Specifications subject to change without notice. 40MPHA-03SM...
  • Page 57 2) Remove the fixing screw (1) on the electronic control box and screws (2) used for the ground connection. T2 Sensor Ribbon 3) Pull upwards until the electronic control box cover is removed. 40MPHA-03SM Specifications subject to change without notice.
  • Page 58 I 4) Remove the fixed devices from the connectors. 5) Disconnect the fan motor connectors, the step motor and the T2 sensor. 6) Open the left side plate of the electronic control box. Specifications subject to change without notice. 40MPHA-03SM...
  • Page 59 Indoor Unit Sizes 18K-24K (Electrical Parts) (Anti-static gloves must be worn) (continued) l l I 7) Open the two clips on the front of the electric box. 8) Open the upper cover plate of the electronic control box. 40MPHA-03SM Specifications subject to change without notice.
  • Page 60 Display board 10) Pull out the electrical main board along the direction indicated in the image on the right. Terminal (1L) Terminal (W) Terminal (S) Pipe Temperature Sensor Room Temperature Sensor Specifications subject to change without notice. 40MPHA-03SM...
  • Page 61 Indoor Unit Sizes 18K-24K (Evaporator) l l I 1) Disassemble the pipe holder located at the rear of the unit. 2) Remove the screw (1) on the evaporator located at the fixed plate. 40MPHA-03SM Specifications subject to change without notice.
  • Page 62 Indoor Unit Sizes 18K-24K (Evaporator) (continued) l l I 3) Release the hook on the evaporator. 4) Remove the screw (1) on the evaporator located at the fixed plate. 5) Remove the evaporator. Specifications subject to change without notice. 40MPHA-03SM...
  • Page 63 1) Remove the screws (2) and remove the fixing board of the fan motor. Screws 2) Remove the bearing sleeve. 40MPHA-03SM Specifications subject to change without notice.
  • Page 64 NOTE: Remove the front panel and electrical parts (refer to the front panel, electrical parts removal steps) before disassembling the step motor. l l I 1) Remove the screws (2), then remove the stepping motor. Stepping Motor Specifications subject to change without notice. 40MPHA-03SM...
  • Page 65: Appendices

    0.27078 18.7177 3.19183 0.80132 0.26408 17.8005 3.07075 0.77709 0.25757 16.9341 2.95896 0.75373 0.25125 16.1156 2.84421 0.73119 0.24512 15.3418 2.73823 0.70944 0.23916 14.6181 2.63682 0.68844 0.23338 13.918 2.53973 0.66818 0.22776 13.2631 2.44677 0.64862 0.22231 40MPHA-03SM Specifications subject to change without notice.
  • Page 66 20.46 5.157 1.674 109.8 19.69 1.632 104.6 18.96 4.849 99.69 18.26 4.703 95.05 17.58 4.562 90.66 16.94 4.426 86.49 16.32 4.294 82.54 15.73 4.167 78.79 15.16 4.045 75.24 14.62 3.927 71.86 14.09 3.812 Specifications subject to change without notice. 40MPHA-03SM...
  • Page 67 163.4 219.2 55.4 109.4 165.2 276.8 57.2 111.2 222.8 278.6 168.8 224.6 280.4 60.8 114.8 170.6 226.4 282.2 62.6 116.6 172.4 228.2 64.4 118.4 174.2 285.8 66.2 120.2 231.8 287.6 177.8 233.6 289.4 40MPHA-03SM Specifications subject to change without notice.
  • Page 68 40MPHA-03SM 2019 Carrier Corporation D 3300 Riverwood Parkway Atlanta GA, 30339 Edition Date: 04/19 Catalog No. 40MPHA-02SM Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Replaces:...

This manual is also suitable for:

40mphaq09xa340mphaq12xa340mphaq18xa340mphaq24xa3

Table of Contents