Toshiba TOSVERT VF-P7 Instruction Manual page 71

Inverter for fan and pump applications
Hide thumbs Also See for TOSVERT VF-P7:
Table of Contents

Advertisement

3) Start and stop (forward run, reverse run, free-run stop) with
 the operating panel and to set the operation frequency by external signals
Title
Function
Operation command

mode selection
Speed setting

mode selection

Panel stop pattern
R/L1
Power
S/L2
supply
T/L3
Operating panel
G/E
CC RX VI
②External volume control
4) Start and stop (forward run, reverse run, free-run stop) and
Title
Function
Operation command

mode selection
Speed setting

mode selection
R/L1
Power
S/L2
T/L3
supply
Control panel
G/E
CC RX VI
②External volume control
[Start/stop]: Press the         key on the
Set value
      operating panel.
(operating panel)
 To switch between forward run and reverse run,
(VI/II)
[Speed command]: By means of external signals
(RR)
(1) VI: 0 to +10 Vdc (0 to +5 Vdc) II: 4 to 20 mAdc
(RX)
(2) RR: Volume / 0 to +10 Vdc (0 to +5 Vdc)
(3) RX: 0 to +/-10 Vdc (0 to +/-5 Vdc)
(Coast stop)
Motor
U/T1
IM
V/T2
W/T3
F
R
The inverter is shipped with
ST
these terminals shorted.
CC
II
RR PP
③0∼±10Vdc
(0∼± 5Vdc)
①0∼+10Vdc
(0∼+ 5Vdc)
①4∼20mAdc
to set the operation frequency by means of external signals
[Start/stop]: Connection and disconnection of terminals
Set value
      F and CC/terminals R and CC.
(Terminal input)
[Speed command]: By means of external signals
(1) VI: 0 to +10Vdc (0 to +5Vdc)/II: 4 to 20mAdc
(VI/II)
(RR)
(2) RR: Volume/0 to +10 Vdc (0 to +5Vdc)
(RX)
(3) RX: 0 to +/-10 Vdc (0 to +/-5Vdc)
Motor
U/T1
IM
V/T2
W/T3
Forward run if ON
F
Slowdown stop if OFF
Reverse run if ON
R
Slowdown stop if OFF
ST
Standby if ON
  Free-run stop if OFF
CC
II
RR PP
③0∼±10Vdc
(0∼± 5Vdc)
①0∼+10Vdc
(0∼+ 5Vdc)
①4∼20mAdc
E-9
RUN
use the forward/reverse run selection .
※Other speed setting
: RX2 (voltage input) (optional)
: 12/16-bit binary input (optional)*
: Serial communication (optional)*
: Serial communication RS485
: Communication add-on(optional)*
: Up-down frequency
: Pulse input (optional)*
*For the setting to be made when using
an asterisked optional device as an
input device, refer to the instruction
manual for the input device used.
As for the action the motor takes
when both the terminals F and R
are connected at the same time,
you can make a selection between
reverse run and a stop.
※Other speed setting
: RX2 (voltage input) (optional)
: 12/16-bit binary input (optional)*
: Serial communication (optional)*
: Serial communication RS485
: Communication add-on(optional)*
: Up-down frequency
: Pulse input (optional)*
*For the setting to be made when using
an asterisked optional device as an
input device, refer to the instruction
manual for the input device used.
STOP
*
=> Refer to 6.2.2
*