       (Continued from the preceding page)
Indication
















(*1)
(Continued on the following page)
Contents
・ Input voltage abnormally varied.
1 Power capacity is 500 kVA or
more.
2 Power-factor improving
capacitor was turned on/off.
Over-voltage
3 Some unit using thyrister is
during fixed
connected with the same
speed
power supply line.
・ Motor falls into regeneration status
because it is rotated fast
exceeding inverter's output
frequency by power of loaded
side.
・ Rapid acceleration is operated.
・ DC breaking rate is too high.
・ V/f parameter is improperly set.
Inverter
・ Running motor is started during
overloaded
momentary power failure status
or so.
・ Load is too heavy.
・ V/f parameter is improperly set.
・ Motor is locked.
Motor
・ Continuous operation in low
overloaded
speed range.
・ Motor is operated with overload.
・ Rapid deceleration is operated.
・ Dynamic braking rate is too high.
Dynamic braking
resistor overload
・ Set over-voltage limit operation
revel parameter  too small.
・ Cooling fan is not actuated.
・ Ambient temperature is too high.
Overheat
・ Vent of cooling fan is shut.
・ Some heat generating matter is
located nearby.
・ Internal thermistor of unit is
disconnected.
Emergency
・ Inverter is stopped by panel operation
stop
during automatic or remote operation.
・ Error occurs during writing data.
EEPROM error
Initial read-error ・ Something abnormal in internal data. ・ Make a service call.
Initial read-error ・ Something abnormal in internal data. ・ Make a service call.
Main RAM fault ・ Something abnormal in control RAM. ・ Make a service call.
Main ROM fault ・ Something abnormal in control ROM. ・ Make a service call.
CPU fault
・ Something abnormal in control CPU. ・ Make a service call.
Interruption
・ Something abnormal occurred
communication
during communication operation.
fault
Gate array
・ Main gate array is abnormal.
fault
Output current
・ Main output current detector is
detector error
abnormal.
・ Something abnormal occurred in
Optional unit
some optional unit (including
fault
abnormal communication [optional
add-on cassettes]).
Flush memory
・ Something abnormal in flush
fault
memory.
・ Output current declined to the
low-current detection level during
low-current
operation.
operation
Expected causes
L-2
Countermeasures
・ Try to insert input reactor.
・ Install dynamic braking resistor.
・ Extend acceleration time #1 .
・ Decrease values of DC injection
braking current  and DC
injection braking time .
・ Check V/f parameter.
・ Use  (Auto-restart) and 
(Regenerative power ride-through control).
・ Raise rating of the inverter.
・ Check V/f parameter.
・ Check loading unit.
・ Reset  properly to motor's
overload reduction start-up
frequency.
・ Extend deceleration time #1 .
・ Increase capacity (wattage) of
dynamic braking resistor and reset
the PBR capacity parameter .
・ Increase the setting value of .
・ After cooling down inverter, reset it
from failure and try to restart it.
・ If cooling fan does not work in
operation, it needs replacement.
・ Secure spaces in the periphery of the
inverter.
・ Don't locate any heat generating thing
near the inverter.
・ Make a service call.
・ Reset the inverter.
・Again turn on the inverter. If it is not
reset, make a service call.
・ Check communication units and their
connections.
・ Make a service call.
・ Make a service call.
・ Check connection of optional
board(s).
・ Refer to instructions of options
concerned.
・ Make a service call.
・ Check to see if low-current detection
level is set properly to the system or
not ().
・ If low-current detection level is
properly set, make a service call.