[Message] The following are messages only. No trip is developed.
Indication
Contents
ST-CC opened

Control circuit

undervoltage
Main circuit

undervoltage
Retry indication

Frequency point

setting error
alarm
Clear enabling

indication
Emergency stop

enabling
indication
Alarm for setup
value error
(Error indication
/
and data are
alternately
displayed twice
each.)
DC braking

indication

Panel indication


overflow
Communication
error
Parameter is

under
initialization.
In auto-tuning

Note: In the case DC injection braking ON/OFF function is selected for an input terminal; if ""
disappears as a result of open-circuit between the terminal and CC, it is normal.
[Pre-alarm display]
Indication
Overcurrent alarm
Overvoltage alarm
Achieving PBR operation level
Overload alarm
Overheat alarm
When two or more alarms occur at the same time, such the message as shown in the following blinks.
, , , ,・・・・・, 
Blinking indications appear in order of , , ,  from the leftmost place to right.
Expected causes
・ ST terminal is in open-circuit.
・ Undervoltage between RO and
SO of control power supply
(when option is used for 22 kW
or lower type).
・ Undervoltage between R, S and
T of main circuit power supply.
・ Trouble of pre-charge circuit
or DC circuit fuse.
・ In retry operation.
・ Momentary power failure is
occurred.
・ Points 1 and 2 of frequency
setting signal are set too close to
each other.
・ If STOP key is pressed after trip
indication, this indication
appears.
・ Stop operation is performed by
panel during automatic or
remote operation.
・ Setup value error is detected in
reading out or writing data.
・ Under DC braking
・ Under motor shaft fixing control
・ Number to be shown on panel
such as frequency and so on
overflows figures of display.
(Number of overflowing digits is
indicated.)
・ Various transmission errors
occur when computer is linked
up with inverter system.
・ Various transmission errors
occur in inverter to inverter
communication (slave side).
Time-out or trip in master side.
・ Parameters are initialized to be
standard default values.
・ Under auto-tuning.
Contents
Same as  (over-current)
Same as  (over-voltage)
P blink while PBR is operating is not an error.
Same as  /  (overload)
Same as  (overheat)
L-4
Countermeasures
・ Close ST-CC circuit.
・ Measure supply voltage of control
power. If voltage is normal, it needs
repair service.
・ Measure supply voltage of main
circuit power. If voltage is normal, it
needs repair service.
・ Make a service call.
・ If inverter automatically restarts
dozens of seconds later, it is
normal. Be careful of inverter in
retry status, because there is a fear
that it may suddenly restart.
・ Set points 1 and 2 of frequency
setting signal apart from each
other.
・ Press STOP key once more for
resetting.
・ If STOP key is pressed, emergency
stop is executed. To cancel
emergency stop, press any other
key.
・ Check setup value for input error.
・ If message disappears dozens of
seconds later, it is normal. (Note)
・ If message disappears by stop
command (ST-CC open), it is
normal.
・ For indication of frequency, set
multiplying rate () lower.
(Parameter setting that results in
overflow is of course valid.)
・ For countermeasures against
various transmission errors, refer to
the "Manual for communication".
・ Check the master inverter.
・ If message disappears dozens of
seconds later, it is normal.
・ If message disappears several
seconds later, it is normal.
Expected causes and countermeasures