Toshiba TOSVERT VF-P7 Instruction Manual page 226

Inverter for fan and pump applications
Hide thumbs Also See for TOSVERT VF-P7:
Table of Contents

Advertisement

[Input terminal function setting (1/2)]
Positive
Negative
Function
logic
logic
0
1
No assignment function
2
3
F: Forward operation command
4
5
R: Reverse operation command
6
7
ST: Standby (Inverse)
8
9
RES: Reset
10
11
S1: Preset-speed #1
12
13
S2: Preset-speed #2
14
15
S3: Preset-speed #3
16
17
S4: Preset-speed #4
18
19
Jog run
20
21
Emergency stop
22
23
DC injection breaking
24
25
Acc/dec switching #1
26
27
Acc/dec switching #2
28
29
V/f switching #1
30
31
V/f switching #2
32
33
Torque limit switching #1
34
35
Torque limit switching #2
36
37
PID control OFF selection
38
39
Pattern group #1
40
41
Pattern group #2
42
43
Pattern group #3
44
45
Pattern group #4
46
47
Pattern run continuation signal
48
49
Pattern run trigger signal
50
51
Forced Jog forward operation
52
53
Forced Jog reverse operation
54
55
Reservation area
56
57
Reservation area
58
59
Reservation area
60
61
Reservation area
62
63
Reservation area
64
65
Reservation area
66
67
Reservation area
68
69
Reservation area
(*1): Valid any time
(*2): Independent of , and all command are valid.
(*3): Dependent on .
: Reservation area. Do not set at these functions.
Sensorless vector/vector with sensor(●: valid,−: invalid)
Speed
Torque
Position
V/f
control
control
control
constant
●/●
●/●
−/●
●/●
●/●
−/●
●/●
●/●
−/●
●/●
●/●
−/●
●/●
●/●
−/●
●/●
●/●
●/●
●/●
●/●
●/●
●/●
−/●
●/●
●/●
●/●
●/●
●/●
●/●
●/●
−/●
●/●
●/●
−/●
●/●
●/●
●/●
●/●
●/●
●/●
●/●
●/●
●/●
Reference
 =
section
(*1)
(*2)
(*2)
(*3)
(*3)
7.2.1

Hide quick links:

Advertisement

Table of Contents
loading