Toshiba TOSVERT VF-P7 Instruction Manual page 35

Inverter for fan and pump applications
Hide thumbs Also See for TOSVERT VF-P7:
Table of Contents

Advertisement

[Standard connection diagram for sink logic(minus common)]
200V class: 30∼55kW
400V class: 30∼90kW
DC reactor (DCL)
Main circuit power supply
200V class(30
55kW):
   3-phase 200
220V-50Hz
       200
230V-60Hz
400V class(30
90kW):
   3-phese 380
440V-50Hz
460V-60Hz
       380
MCCB
*1: Connect a power source for
the control circuit.
*2: The inverter is shipped with
the terminals PO and PA
shorted with a bar. Remove
this shorting bar when
installing a DC reactor (DCL).
*3: Power output for the control
circuit, which is provided
only for the 400V 45kW
and larger models.
Single-phase
207.5∼220V-50Hz
207.5∼230V-60Hz
(10VA)
Digital
voltmeter
Voltmeter or ammeter
*4: Connections of control power cables by voltage for the
400V 45kW and larger models.
Single-phase 415∼440V-50Hz
415∼460V-60Hz
R46
R41
Control
circuit
S0
R20
S20
*2 (Optional)
PO
R/L1
S/L2
T/L3
R0
Control
*1
circuit
S0
(R20)
*4
*3
(S20)
FLA
FLB
FLC
P24
OUT1
Ry
OUT2
Ry
G/E
FP
FM
AM
Frequency
Ammeter
meter
Single-phase 380∼415V-50/60Hz
R46
R41
S0
R20
S20
Braking unit PB3
(Optional)
PA
PB
PC
Main circuit
*4
Control panel
FL
SINK
Connector for
common serial
SOURCE
communication
RS485 connector
for serial
communication
CC
RX VI RR PP
External potentiometer
(or voltage signal between RR and CC: 0∼10V)
Control
circuit
B-4
☆ When the built-in
dynamic braking circuit
(GTR7) is modified to
connect an external
dynamic braking resistor
PA
PB
Motor
U/T1
V/T2
IM
W/T3
F
Forward
Reverse
R
ST
Standby
RES
Reset
Preset
S1
speed 1
Preset
S2
speed 2
Preset
S3
speed 3
Preset
S4
speed 4
CC
Common
Current signal
II
Voltage signal:-10∼+10V
Voltage signal:0∼10V
PC
Factory
default
settings
:4∼20mA