Standard Connection - Toshiba TOSVERT VF-P7 Instruction Manual

Inverter for fan and pump applications
Hide thumbs Also See for TOSVERT VF-P7:
Table of Contents

Advertisement

2.2 Standard connection

-Do not connect the power cables to any output terminal (U/T1, V/T2 or W/T3 on the
motor side), or the inverter could break down and cause a fire.
-Do not connect a resistor to any D.C. terminal (between PA and PC or PO and PC), or
Prohibited
the inverter could cause a fire.
To install external braking resistor, refer to 6.13.4.
-Connect grounding wires correctly and securely. Failure to do so could cause an
electric shock or a fire if current leakage occurs or the inverter breaks down.
Be Grounded
[Standard connection diagram for sink logic(minus common)]
200V class: 18.5∼22kW
400V class: 18.5∼22kW
Main circuit power supply
200V class(18.5∼22kW):
   3-phase 200∼220V-50Hz
   3-phase 200∼230V-60Hz
400V class(18.5∼22kW)
   3-phase 380∼460V-50/60Hz
MCCB
* When using a separate power source
for the control circuit
For the 22kW and smaller models,
power is supplied to the control circuit
from the main circuit. An optional device
is required to
CN21
supply from
another source.
(though
Control circuit
terminals only
Option
are provided.)
*1: The control power supply terminals
RO and SO are optionally
available for the 22kW and
smaller models. Though terminals
RO and SO are fitted as
standard for the 22kW and
smaller models as well, they
are not connected internally.
*2: The inverter is shipped with
the terminals PO and PA
shorted with a bar. Remove
this shorting bar when installing
a DC reactor (DCL).
Digital
voltmeter
DC reactor (DCL)
*2 (Optional)
PA
PO
R/L1
S/L2
T/L3
R0
Control
Note
CN21
circuit
*1
S0
FLA
FLB
FLC
P24
OUT1
Ry
OUT2
Ry
G/E
FP
FM
AM
Frequency
Ammeter
meter
Voltmeter or ammeter
Danger
Dynamic braking resistor
(Optional)
PB
PC
U/T1
V/T2
Main circuit
W/T3
FL
Control panel
Connector for
common serial
communication
SINK
RS485 connector
for serial
SOURCE
communication
CC
RX VI RR PP
External potentiometer
(or voltage signal between RR and CC: 0∼10V)
B-3
Motor
IM
Forward
F
Reverse
R
ST
Standby
RES
Reset
Preset
S1
speed 1
Preset
S2
speed 2
Preset
S3
speed 3
S4
Preset
speed 4
Common
CC
Current signal
II
:4 to 20mA
Voltage signal:-10∼+10V
Voltage signal: 0∼10V
Factory
default
settings