Under-voltage
(main circuit)

(*1)
Under-voltage

(control circuit)
(*1)
Over-torque


Ground-fault

Auto-tuning

error
Inverter type

error
Sink/source

switching error
 Sequence error
 Encoder error
Speed error

(Over speed)
To much
potential

deviation
 Key error
 VI/II input error
Presence or absence of parameter trip can be selected.
(Note) Please contact us if you find any trips other than the above.
Expected causes
・ Input voltage (main circuit)
becomes insufficient in operation.
・ Momentary power failure occurs
because undervoltage continues
longer than under-voltage
detection time .
・ Input voltage (control circuit)
becomes insufficient in operation.
・ Momentary power failure occurs
because undervoltage continues
longer than under-voltage
detection time .
・ Load torque reaches over-torque
detection level in operation.
・ Output cable or motor falls into
ground-fault.
・ Check settings of  to  parameters for motor.
・ Motor whose capacity is smaller by two or more ranks than that of inverter
is used, isn't it?
・ Extremely think cable is used as inverter output cable, isn't it?
・ Motor is running, isn't it?
・ Motor other than three-phase inductive type is used, isn't it?
・ If  error occurs as power is turned on, set motor type parameter as
 =  (others).
・ Is control board (or drive board of
main circuit) replaced?
・ Sink/source switch of
input/output terminal is set wrong
(reversely switched on/off).
・ The signal from a system is not
inputted into input terminals.
・ The input terminal function (
or ) is not set up.
・ For not using the system-
supporting sequence 
function, it is set up except 0.0 at
.
・ Disconnection of encoder circuit.
・ Something abnormal in encoder
(inverter)
・ Potential deviation exceeded the
 set value during position
control.
・ RUN or STOP key is depressed
for 5 seconds or more.
・ Key is faulty.
・ Breaking down of a wire for VI/II
input signal.
L-3
Countermeasures
・ Check input voltage.
・ If undervoltage is detected, set
 (regenerative power ride-
through control),  (auto-restart)
and  (under-voltage detection
time) as countermeasures against
future momentary power failure.
・ Check input voltage.
・ If undervoltage is detected, set
 (regenerative power ride-
through control),  (auto-restart)
and  (under-voltage detection
time) as countermeasures against
future momentary power failure.
・ Check the system if there is
something abnormal in it or not.
・ Check units and connections if there
is ground-fault or not.
・ When board has been replaced, input
 for .
・ Check connections and set proper
logic.
・ After making sure that sequence is
normal, proceed in operation.
・ If the same error does not occur when
the power is turned on again, the
system has recovered normal status.
(Check control terminals and
sink/source switches including those
of add-on options.)
・ Please check if the sequence is
normal or not.
・ Please set  or  as the input
terminal to use.
・ Please set up 0.0, when you do not
use system-supporting sequence.
・ Check connection of encoder.
Connect encoder correctly.
・ Check connection of encoder.
Connect encoder correctly.
・ Check connection of encoder.
・ Increase the setting value of .
・ Adjust the parameters on position
control
・ Check operation panel.
・ Check VI/II input signal