Toshiba TOSVERT VF-P7 Instruction Manual page 234

Inverter for fan and pump applications
Hide thumbs Also See for TOSVERT VF-P7:
Table of Contents

Advertisement

(Continued from the preceding page)
Item
Stall prevention during operation, over-current suppression, overload, power
Warning
source-side undervoltage (optional), DC circuit undervoltage, setting error, retry in
message
process, upper/lower limits.
Overcurrent, over-voltage, heat sink overheat, load-side short-circuit, load-side ground
Fault
fault, inverter overload, armature over-current during start-up, load-side over-current
causes
during start-up, EEPROM error, RAM error, ROM error, transfer error (dynamic braking
trouble
resistor overload), (emergency stop), (undervoltage), (weak current), (over-torque),
(motor overload), (output open-phase). Items in parentheses are selectable.
Operation frequency, operation frequency command, operating direction
(forward/reverse), output current, DC voltage, output voltage, compensated frequency,
terminal board input /output information, CPU version, control EEPROM version, tripping
history, cumulative operation time, speed feedback, torque, torque command, torque
4-digit
Monitoring
current, exciting current, PID feedback value, motor overload rate, inverter overload rate,
7-segment
PBR overload rate, PBR load rate, power supply, output current, peak output current,
function
LED
peak DC voltage, motor counter pseudo PG, position pulse, RR input, VI/II input, RX
input, RX2 input, FM output, AM output, fixed output for meter adjustment, flash memory
version, main circuit EEPROM version, connection option types, previous default setting,
previous automatic control (AU2), sink/source switching status.
Can select frequency display to match motor speed, line speed, etc. Selection of
Selectable
unit display
display of current in amperes/%, voltage in voltage/%.
Edit
Parameters different from those set by default are retrieved automatically, so that
function
parameters changed can be detected easily.
User
Original parameters set by user can be stored. Parameters stored can be reset to
settings
original user-defined parameters.
initialization
Charge
Indicates that main circuit capacitors are charged.
LED
indicator
Input/output terminal
A-contact/B-contact switchable by making a selection from the programmable I/O
logic switching
terminal function menu. (*1), (*2) (Default setting: A-contact)
Sink/source
Negative common (CC) and positive common (P24) of control terminal are switchable to
switching
each other. (On shipment, negative common [CC] is selected as default setting.)
Fault detection signal 1c contact output (250Vac-2A-cosΩ = 1,250Vac-1A-cosΩ = 0.4, 30Vdc-1A)
Low-speed/speed
reach signal
Open-collector output (24Vdc, Max. 50mA, output impedance: 33Ω)
output (*2)
Upper/lower limit
frequency output
Open-collector output (24Vdc, Max. 50mA, output impedance: 33Ω)
(*2)
Frequency meter
output/ammeter
Analog output, 1mAdc full-scale ammeter or 7.5Vdc-1mA voltmeter.
output (*3)
Pulse train
Open-collector output (24Vdc, Max. 50mA)
frequency output
RS485 equipped as standard (connector: modular 8P, optional device required for
Communication
communication with more than one unit)
functions
RS232C, TOSLINE-F10M and TOSLINE-S20 are optional. DeviceNet and ProfiBus
are on the drawing board.
Service
Indoor, altitude 1000m or less, not subject to direct sunlight or corrosive/explosive
gas or steam.
environment
Ambient
-10 to +50°C
temperature
Storage temperature -25 to +65°C
20 to 93% (no condensation allowed)
Relative humidity
5.9m/s2 {0.6G} or less (10 to 55Hz) (according to JIS C0911)
Vibration
(*1):
The 16 contact-input terminals (8 of which are optional) are programmable. For each of them, a signal
can be selected from among 136 signals.
(*2):
For each programmable ON/OFF output terminal, a signal can be selected from among 120 signals.
(*3):
For each programmable analog output terminal, a signal can be selected from among 32 signals.
(*4):
When the cover is removed, the unit must be placed in the panel to prevent the charger from being
exposed. For the 30kW and larger models, the unit can be used in a temperature range of -10 to
+50°C with the cover left attached.
(*5):
The models with a capacity of 30kW or more have uncovered wide-opened wiring holes and the unit
has no space in it which is large enough to bend external cables. So, use a optional wiring hole covers
when installing the unit outside.
(*6):
Protect the inverter from over-current caused by output-side ground fault.
Description
K-4