Input Jumper Settings
The tables below show how to set a specific jumper to change input functionality. To access the I/O
jumpers, you must open the controller according to the instructions beginning on page 13.
▪ Incompatible jumper settings and wiring connections may seriously damage the controller.
Digital Inputs 0-11: Set Type
Set to
npn (sink)
pnp (source)*
Inputs 7/8: Set Type - Digital or RTD/TC #1
Set to
Digital*
Thermocouple
PT100
Inputs 9/10: Set Type - Digital or RTD/TC #0
Set to
Digital*
Thermocouple
PT100
Input 11: Set Type - Digital or CM for PT100
Set to
Digital*
CM for PT100
Input 5: Set Type - Digital or Analog #3
Set to
Digital*
Voltage
Current
Input 6: Set Type - Digital or Analog #2
Set to
JP8
Digital*
A
Voltage
B
Current
B
*Default settings
8
JP12 (all Inputs)
A
B
JP1
JP2
JP3
A
A
A
B
B
B
B
A
B
JP5
JP6
JP7
A
A
A
B
B
B
B
A
B
JP11
A
B
JP4
JP10
A
A
B
A
B
B
JP9
A
A
B
Vision™PLC+HMI Installation Guide
Analog Output 0: Set to Voltage/Current
Set to
JP13
Voltage*
A
Current
B
Analog Output 1: Set to Voltage/Current
Set to
JP14
Voltage*
A
Current
B
Unitronics