Alternative power cable types

Power cable types that can be used with the drive are represented below.
Recommended
Symmetrical shielded cable: three phase
conductors and a concentric or otherwise
symmetrically constructed PE conductor, and a
shield
PE conductor
and shield
A four-conductor
system: three phase
conductors and a
protective conductor
The following power cable type is not allowed.
PE

Motor cable shield

To effectively suppress radiated and conducted radio-frequency emissions, the
shield conductivity must be at least 1/10 of the phase conductor conductivity. The
requirements are easily met with a copper or aluminum shield. The minimum
requirement of the motor cable shield of the drive is shown below. It consists of a
concentric layer of copper wires with an open helix of copper tape or copper wire.
The better and tighter the shield, the lower the emission level and bearing currents.
Insulation jacket
Shield
PE
PE
Not allowed for motor cables
Symmetrical shielded cable with individual shields for each phase conductor
is not allowed on any cable size for input and motor cabling.
Copper wire screen
Planning the electrical installation 55
A separate PE conductor is required if the
conductivity of the cable shield is < 50%
of the conductivity of the phase
conductor.
Not allowed for motor cables with
phase conductor cross section larger
than 10 mm
Helix of copper
tape or copper wire
Shield
PE
Shield
2
[motors > 30 kW (40 hp)].
Inner insulation
Cable core