98 Maintenance
LEDs
This table describes LEDs of the drive.
Where
RMIO board
Control panel mounting
platform
AINT board
LED
Red
Drive in fault state
Green
The power supply on the board is OK.
Red
Drive in fault state
Green
The main + 24 V power supply for the control panel
and the RMIO board is OK.
V204 (green)
+5 V voltage of the board is OK.
V309 (red)
Prevention of unexpected start-up (option +Q950)
or Safe torque off (option +Q967) is ON.
V310 (green)
IGBT control signal transmission to the gate driver
control boards is enabled.