Cable Types - ABB ACS800-04 Hardware Manual

Drive modules
Hide thumbs Also See for ACS800-04:
Table of Contents

Advertisement

118 Technical data

Cable types

Cable sizing is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire
insulation at 40 °C (104 °F) ambient temperature. Not more than three current-
carrying conductors in raceway or cable or earth (directly buried). For other
conditions, dimension the cables according to local safety regulations, appropriate
input voltage and the load current of the drive.
Copper cables with concentric copper shield
Max. load
current
A
57
75
88
101
114
132
154
176
202
224
250 MCM or 2 × 1
251
300 MCM or 2 × 1/0
273
350 MCM or 2 × 2/0
295
400 MCM or 2 × 2/0
334
500 MCM or 2 × 3/0
370
600 MCM or 2 × 4/0 or 3 × 1/0
405
700 MCM or 2 × 4/0 or 3 × 2/0
449
2 × 250 MCM or 3 × 2/0
502
2 × 300 MCM or 3 × 3/0
546
2 × 350 MCM or 3 × 4/0
590
2 × 400 MCM or 3 × 4/0
669
2 × 500 MCM or 3 × 250 MCM
739
2 × 600 MCM or 3 × 300 MCM
810
2 × 700 MCM or 3 × 350 MCM
884
3 × 400 MCM or 4 × 250 MCM
1003
3 × 500 MCM or 4 × 300 MCM
1109
3 × 600 MCM or 4 × 400 MCM
1214
3 × 700 MCM or 4 × 500 MCM
Cable type
AWG/kcmil
6
4
3
2
1
1/0
2/0
3/0
4/0

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs800-04mAcs800-u4

Table of Contents