3.5.1 Auto-Discovery: After Completion
NOTE: If Modbus TCP/IP was selected in Section
section. Auto-Discovery is NOT used for Modbus TCP/IP.
The S3 DIP Switch for Enabling Auto-Discovery should have been set in Section
power to the ProtoNode. Do not Enable Auto-Discovery when the unit is powered.
When power is applied to a ProtoNode that is set to Enable Auto-Discovery, it will take 3 minutes
to complete the discovery of all of the RS-485 devices attached to the ProtoNode.
The "TX" LED will flash during Auto-Discovery. The "TX" LED will stop flashing when completed.
Once the ProtoNode has discovered all of the RS-485 devices, set the S3 DIP switch to the
OFF position to save the current configuration.
Then turn the power to the ProtoNode back ON. The stored configuration will be loaded.
Auto-Discovery ON – Build New Configuration
Auto-Discover OFF – Save Current Configuration

Figure 19: S3 DIP Switch setting for Auto Discovering Devices

S3 DIP Switch Auto-Discovery Mode
Page 21 of 50
Turn Off to Save Configuration