Appendix A.5. Update Firmware

To load a new version of the firmware, follow these instructions:
1. Extract and save the new file onto the local PC.
2. Open a web browser and type the IP Address of the FieldServer in the address bar.
NOTE: Default IP Address is 192.168.1.24
NOTE: Use the FS Toolbox utility if you do not know the IP Address
3. Click on the "Diagnostics & Debugging" button.
4. In the Navigation Tree on the left hand side, do the following:
a. Click on "Setup"
b. Click on "File Transfer"
c. Click on the "Firmware" tab
5. In the Firmware tab, click on "Choose Files" and select the firmware file extracted in step 1.
6. Click on the orange "Submit" button.
7. When the download is complete, click on the "System Restart" button.

Appendix A.6. BACnet: Setting Network_Number for more than one ProtoNode on Subnet

For both BACnet MS/TP and BACnet/IP, if more than one ProtoNode is connected to the same subnet,
they must be assigned unique Network_Number values.
On the main Web Configuration screen, update the Network Number with the "network_nr" field and click
submit. The default value is 50.
Figure 30: Web Configurator
Setting Network Number for BACnet
Page 36 of 50
ProtoNode Startup Guide
(Appendix A.1)