PV Value for Error 0002H
Input Sensor Did Not Connect
PV Value for error 0003H
Input Signal Error
PV Value for Error 0004H
Over Input Range
ADC Fail
PV Value for Error 0006H
EEPROM Read/Write error
NOTES:
"Process Value" Codes: XXX.X=actual value; 8002H=initial process; 8003H=temperature sensor is not connected; 8004H=temperature sensor
1)
input error; 8006H=Cannot get temperature value. ADC input error; 8007H=Memory read/write error.
"Control Mode" Codes: 0=PID; 1=On/Off; 2=manual tuning; 3=PID program control
2)
"Alarm Types" Codes: 0=alarm function disabled; 1=deviation upper- and lower-limit; 2=deviation upper-limit; 3=deviation lower-limit; 4=reverse
3)
deviation upper- and lower-limit; 5=absolute value upper- and lower-limit; 6=absolute value upper-limit; 7=absolute value lower-limit; 8=deviation
upper- and lower-limit with standby sequence; 9=deviation upper-limit with standby sequence; 10=deviation lower-limit with standby sequence;
11=hysteresis upper-limit alarm output; 12=hysteresis lower-limit alarm output; and 13=CT alarm output
"Setting Lock Status" Codes: 0=normal; 1=all setting lock; 11=lock others than SV value
4)
"Communication Write In" Codes: 0=disabled; 1=enabled
5)
"Temperature Unit Display Selection" Codes: 0= ° F; 1= ° C
6)
"Control RUN/STOP Setting" Codes: 0=STOP; 1=RUN
7)
"STOP setting for PID program control" Codes: 0=RUN; 1=STOP
8)
"Temporary STOP for PID program control" Codes: 0=RUN; 1=temporary STOP
9)
AI
32
AI
32
AI
33
AI
33
AI
34
AI
34
AI
35
AI
35
AI
36
AI
36
AI
37
AI
37
AI
38
AI
38
AI
39
AI
39
AI
40
AI
40
Page 42 of 50
nvoPVValEr2H_XXX
SNVT_count_inc_f
nvoInSnNoCnc_XXX
SNVT_count_inc_f
nvoPVValEr3H_XXX
SNVT_count_inc_f
nvoInSigErr_XXX
SNVT_count_inc_f
nvoPVValEr4H_XXX
SNVT_count_inc_f
nvoOvrInRng_XXX
SNVT_count_inc_f
nvoADC_Fail_XXX
SNVT_count_inc_f
nvoPVValEr6H_XXX
SNVT_count_inc_f
nvoEEPROMErr_XXX
SNVT_count_inc_f
ProtoNode Startup Guide
DA_U16_XXX
31
DA_U16_XXX
32
DA_U16_XXX
33
34
DA_U16_XXX
DA_U16_XXX
35
DA_U16_XXX
36
DA_U16_XXX
37
DA_U16_XXX
38
DA_U16_XXX
39