2.4 Selecting the Desired Field Protocol and Enabling Auto -Discovery
2.4.1 Selecting Desired Field Protocol
•
ProtoNode FPC-N34 units use the "S" bank of DIP switches (S0 – S2) to select the Field
Protocol.
o
See the table in
o
The OFF position is when the DIP switches are set closest to the outside of the box.
•
ProtoNode FPC-N35 units do not use the "S" bank DIP switches (S0 – S2) to select a Field
Protocol.
o
On ProtoNode FPC-N35 units, these switches are disabled; the Field Protocol is always
LonWorks.
S 0
S1
S 2
S 3
–
S0
Switches
BACnet/IP
BACnet MS/TP
Metasys N2
Modbus TCP/IP
BACnet MS/TP (single node)
NOTE: When setting DIP Switches, please ensure that power to the board is OFF.
Figure 5
for the switch settings for the ProtoNode.
S3 DIP
ProtoNode FPC-N34
Profile
Profile Settings for ProtoNode
Figure 5: S Bank DIP Switches
Page 10 of 50
ProtoNode Startup Guide
S Bank DIP Switch Location
S Bank DIP Switches
S0
S1
S2
Off
Off
Off
On
Off
Off
Off
On
Off
On
On
Off
Off
Off
On