1

Overview

• Connection to a building management system via BACnet / IP or Modbus / TCP
• Internal memory for data logging
• Automatic firmware updates via Internet
• Suitable for all controllers with S-Bus
• WLAN functionality
Technical data
Housing: plastic
Ingress protection: IP 20 / EN 60529
Protection class: III
Ambient temperature: 0 ... 40 °C
Maximum altitude: 2000 m above MSL
Relative humidity: 10 ... 90 %
Dimensions: 95 × 70 × 25 mm
Mounting: wall mounting (optional)
Display: operating control LED
Interfaces: S-Bus for the connection to the controller, 10/100 Base TX Ethernet,
Auto MDIX, WLAN 2.4~2.4835 GHz
WLAN encryption: WPA / PSK, WPA2 / PSK
Transmit power limit (e.i.r.p.): < 100 mW
Power consumption: < 1.75 W
Power supply:
Mains adapter: 100 – 240 V~, 1A / 12 V ⎓ , 1 A (Level 6)
Regtronic KM IP:12 V ⎓ , 120 mA
Electrical energy source: ES1 (EN 62368-1)
Electrical power source: PS1 (EN 62368-1)
Thermal energy source: TS1 (EN 62368-1)
Mechanical energy source: MS1 (EN 62368-1)
Use mains adapter in dry interior
Mains adapter protection class: II
rooms only.
2

Scope of delivery

If one of the items mentioned below is missing or defective, please contact your
distributor:
1 Regtronic KM IP incl. mains adapter, S-Bus cable pre-connected
2 Interchangeable mains adapter plugs (EURO, UK, USA, AUS)
3 Network cable (CAT5e, RJ45), 2 m
4 Wall plugs, screws and rubber pads
Manual (not illustrated)
Coaxial connector polarity:
internal: plus
external: minus (GND)
1
2
4
3
25