oventrop Aktor M ST Operating Instructions Manual

oventrop Aktor M ST Operating Instructions Manual

Electromotive actuator 24 v

Advertisement

Quick Links

Valves, controls + systems
Electromotive actuator
EN
"Aktor M ST/2P/3P L", 24 V
Operating instructions

Advertisement

Table of Contents
loading

Summary of Contents for oventrop Aktor M ST

  • Page 1 Valves, controls + systems Electromotive actuator “Aktor M ST/2P/3P L”, 24 V Operating instructions...
  • Page 3: Table Of Contents

    Electromotive actuator 24 V Contents Contents Page General information ........................4 Validity of the operating instructions ..................4 Type plate ..........................4 Extent of supply ........................4 Contact ............................4 EU Declaration of conformity ....................4 Used symbols ..........................4 Safety-related information ......................4 Correct use ..........................4 Warnings ...........................4 Safety notes ..........................5 2.3.1 Danger in case of inadequate personnel qualification ................
  • Page 4: General Information

    Each warning contains the following elements: • “Aktor M ST/2P/3P L” 24V Warning symbol SIGNAL WORD • Operating instructions Type and source of danger Contact Possible consequences if the danger occurs Address or the warning is ignored. f Possibilities of avoiding the danger. OVENTROP GmbH & Co. KG Paul-Oventrop-Straße 1 Signal words define the seriousness of the danger 59939 Olsberg which arises from a situation. GERMANY DANGER Technical service Indicates an imminent danger with high risk. Phone: +49 (0) 29 62 82-234 The situation will lead to death or serious injury if not avoided.
  • Page 5: Safety Notes

    Electromotive actuator 24 V Safety-related information Safety notes We have developed this product in accordance with current safety requirements. Please observe the following notes concerning safe use. 2.3.1 Danger in case of inadequate personnel qualification Any work on this product must only be carried out by qualified tradespeople. As a result of their professional training and experi- ence as well as their knowledge of the relevant legal regulations, qualified tradespeople are able to carry out any work on the described product professional- User The user has to be informed by the qualified trades- people as to the operation. 2.3.2 Risk of burns due to hot components and surfaces...
  • Page 6: Technical Description

    Technical description Electromotive actuator 24 V Technical description Functional description The actuator opens or closes the valve depending on Construction the applied control voltage. Technical data 68.5 Operating voltage 24 V AC ±10 %, 50/60 Hz 24 V DC ±10 % Power consump- Dimensioning: tion - 8.5 VA (24 V AC) - 4.1 W (24 V DC) Nominal: - 4.0 VA (24 V AC)
  • Page 7: Transport And Storage

    Electromotive actuator 24 V Transport and storage 1. Fit the adapter set to your valve according to the Protection class IP54 enclosed installation instructions. Protective system III according to EN 60730 2. Fit the actuator to the connection thread of the Installation posi- 360° adapter.
  • Page 8: Connection Of The Power Supply

    Installation Electromotive actuator 24 V f Connect the power supply. 2..10 V DC 0..10 V DC Z After having connected the power supply for the Control range of the steady control signal. first time, the actuator will carry out an initialisation Setting of the travel direction with a control volt- run. age of 10 V DC The product will be ready for operation after initiali- Travel direction and Travel direction and po- sation. position feedback sition feedback 0..100 Z Protect the stroke position indicator by turning the 100...0 %...
  • Page 9: Control

    Electromotive actuator 24 V Operation Manual setting 5.4.3 Control NOTICE Damage to the actuator due to manual po- sitioning of the stem beyond the defined range The actuator can be damaged and its func- tion be impaired during manual setting. f Only move the adjustment stem with little 24 V AC/DC force.
  • Page 10: Removal

    Removal Electromotive actuator 24 V Removal 7. Remove the actuator from the valve. Also remove the adapter set if you do not re- quire it any longer for this valve. Reinstallation The actuator must not be in the lower stroke position for correct installation. 1. Before reinstallation, move the actuator to an upper to medium stroke position with the help of a control signal or the manual setting (see section 6.3). 2.