6.7 Human Detect control
The Human detect sensor is optional.
The operation mode of human detect control can be set by controller (N50).
1) When set the mode "Used to adjust the set temperature when unattended" and enter the unattended state
following logic is executed
① When the cooling/automatic cooling mode operates, the correction value
minute.
② During heating/automatic heating mode operation, the correction value of the set temperature Ts is - 1 every A
minute;
③ Fan speed 1
④ The fan louver maintains the previous angle.
⑤ Resume normal control when someone is detected
2) When set the mode " Used to turn off the unit when unattended " and enter the unattended state
logic is executed
① Turn off the unit
② Resume normal control when someone is detected
Note:
1. The unattended state will only be entered after the unattended state is detected for X minutes. X can be set by the controller (N53)
2. The value of maximum temperature adjustment can be set by controller (N52)
3. The value of A can be set by controller (N51)
2
of the set temperature Ts is + 1 every A
1
, the
3
1
, the following