Download Print this page

Sinclair SDV 6 Service Manual page 16

Full dc inverter systems

Advertisement

Table 3.4: Duct main PCB ports (continued)
Label in
Code
Figure 3.3
7
CN81
8
CN82
9
CN83
10
CN-A
11
CN30
12
CN35
13
CN5
14
CN190
15
CN18
16
CN16
17
CN25
CN8
18
19
CN55
20
CN6(X1X2,PQE)
21
CN2(D1D2)
22
CN10(M1M2)
23
CN99
Notes:
1.
Standard: The port is standard, the customers can connect corresponding device through this port, such as water pump and Humidity sensor etc.
Customized: The port is not available on the mainboard. If necessary, you need to customize the port
Reserved: This port can not be used.
2.
When repairing, PQ connects after-sales tooling
3.
PQ and M1M2 communication ports both are used for indoor and outdoor communication, and only one of them can be used at a tim e. Meanwhile, be
sure to connect the same communication ports (PQ to PQ; M1M2 to M1M2) in case of damage of the main control board.
4.
D1D2 communication ports are used for group control communication. When connecting the group controller, the D1D2 port of the indoor units that are
to be group controlled must be connected in daisy chain, and the group controller must be connected to the X1X2 port of one of the indoor units in t he
group control, and set to group control mode. In addition, D1D2 communication ports can also be connected to the central controller.
5.
Refer to Table 3.2 for voltage test instructions of some ports.
T2 Temperature sensor connection
T1 Ambient Temperature sensor connection
T2B Temperature sensor connection
Sterilization module port
Display Panel connection
Humidity sensor connection
Water level port
Drainage pump port
Switch Board
Reserved
Program burning port(indoor unit)
EEV drive port
Remote on/off switch connection
X1 X2 communication port(with wire controller);
P Q communication port(with ODU by RS-485)
D1 D2 communication port(with Central controller)
M1 M2 communication port(with ODU by HyperLink)
After-sale Kit communication port
Content
Port voltage
3.3V DC
Standard
3.3V DC
Standard
3.3V DC
Standard
12V DC
Standard
[5]
12V DC
Standard
[5]
3.3V DC
Standard
[5]
3.3V DC
Standard
12V DC
[5]
Standard
[5]
5V/12V DC
Standard
12V DC
Reserved
[5]
3.3V DC
Standard
Standard
12V DC
[5]
Note 5
Standard
X1 X2:18V DC ;
P,E or Q,E:
Standard
2.5-2.7V DC
D1,E or D2,E
Standard
2.5 - 2.7V DC
24V DC
Standard
[5]
12V DC
Standard
Note