8.1.6 A73 - The error of the linked FAPU is transmitted to the master IDU (non-series connection)
Note:
1) The type of FAPU may be HRV, VRF fresh air IDU and so on.
2) Series setting: The linked FAPU and the master IDU are connected to the air supply duct and air return duct respective ly and
separately. A wired controller is used to set this installation method as a non-series connection.
Error display
Error impact
Error trigger
Error recovery
Possible cause
Troubleshooting
64
Digital display
Master IDU: operates normally. FAPU: stops. Other IDUs of the same system: operate normally.
ODU of the same system: operate normally.
The error of the linked FAPU is transmitted to the master IDU
Automatic recovery
The FAPU is faulty.
The master IDU's main control board is damaged.
Obtain the linked error code (1)
of the FAPU, and refer to the
correspon ding error han dling
method in the maintena nce
manua l of the FAPU for
trouble sho otin g
Erro r in FAPU
Afte r troub leshooting, is the
master IDU error
code cl eared?
Note:
1. The error code can be queried after the FAPU is connected to the wired controller or the display
box.
Panel or display box
Spot check interface
A71/A73
No
Yes
Fault clear ed
Display position (master IDU)
Wired controller
Error code is not
query
displayed
Replace th e the main co ntr ol
boa rd o f th e master IDU