6.13 Dry mode control
There is a difference between the control with humidity sensor and the control without humidity sensor, when the
humidity sensor is damaged, the indoor unit automatically switches to the state without humidity sensor.
Without humidity sensor
Related settings: ①The temperature of dry mode;②Maximum indoor temperature drop in dry mode (N27);③Standby
fan speed in dry mode(N19)
Enter Standby: When Ts-T1>ΔT, the IDU will Enter Dry standby mode.
Fan speed (operation): Automatic adjustment, cannot be set.
Fan speed (Standby): Can be set by controller (N19)
With humidity sensor(customized)
Related settings: ①The temperature and humidity of dry mode;②Maximum indoor temperature drop in dry mode;③
Standby fan speed in dry mode
Enter Standby: When Ts-T1>ΔT or actual humidity is lower than the set humidity 5%, the IDU will Enter Dry standby mode.
Fan speed (operation): Automatic adjustment, cannot be set
Fan speed (Standby): Can be set by controller (N19)
Note:
1. Ts: Dehumidification setting temperature
2. T1: IDU air return temperature
3.ΔT: Maximum indoor temperature drop,can be set(N27)
Auto dry function
Prerequisites for function:①Only IDU with humidity sensor (customized) can use this function.
②Need to enter the IDU parameter setting menu to
Entry method: Cooling or Auto mode.
Operation Logic: Priority cooling, when the room temperature reaches the set temperature, automatically switch to dry
mode, to approximate the purpose of dual control of temperature and humidity.
Note:
1. For Auto Dry Target relative humidity, the Default value is 65% and can be set (N67).
52
enable this function
(N66).