Download Print this page

Sinclair SDV 6 Service Manual page 28

Full dc inverter systems

Advertisement

Table 3.10: High Static Pressure Duct main PCB ports (continued)
Label in
Code
Figure 3.9
9
CN81
10
CN82
11
CN83
12
CN5
13
CN25
14
CN-A
15
CN190
16
CN8
17
CN18
18
CN30
19
CN55
CN6(X1X
20
2,PQE)
CN2(D1D
21
2)
CN10(M1
22
M2)
23
CN99
Notes:
1.
Standard: The model has this function, the customers can connect corresponding device through this port, such as water pump and hotel key card etc.
Customized: This function needs to be customized before leaving the factory.
Reserved: This port can not be used.
2.
When repairing, PQ connects after-sales tooling
3.
PQ and M1M2 communication ports both are used for indoor and outdoor communication, and only one of them can be used at a time. Meanwhile, be
sure to connect the same communication ports (PQ to PQ; M1M2 to M1M2) in case of damage of the main control board.
4.
D1D2 communication ports are used for group control communication. When connecting the group controller, the D1D2 port of the indoor units th at are
to be group controlled must be connected in daisy chain, and the group controller must be connected to the X1X2 port of one of the indoor units in the
group control, and set to group control mode. In addition, D1D2 communication ports can also be connected to the central controller.
5.
Refer to Table 3.2 for voltage test instructions of some ports.
Content
T2 Temperature sensor connection
T1 Ambient Temperature sensor connection
T2B Temperature sensor connection
Water level port
Program burning port(indoor unit)
Sterilization module port
Drainage pump port
EEV drive port
Switch Board
Display Panel connection
Remote control ON/OFF port
X1 X2 communication port(with wire controller);
P Q communication port(with ODU by RS-485)
D1 D2 communication port(with Central controller)
M1 M2 communication port(with ODU by HyperLink)
After-sale Kit communication port
Port voltage
Note
3.3V DC
Standard
3.3V DC
Standard
3.3V DC
Standard
[5]
3.3V DC
Standard
[5]
3.3V DC
Standard
12V DC
Reserved
[5]
12V DC
Standard
12V DC
[5]
Standard
[5]
5V/12V DC
Standard
12V DC
[5]
Standard
Note 5
Standard
X1 X2:18V DC ;
P,E or Q,E:
Standard
2.5-2.7V DC
D1,E or D2,E
Standard
2.5 - 2.7V DC
24V DC
Standard
[5]
12V DC
Standard
25

Advertisement

loading