Table 3.11: High Static Pressure Duct main PCB ports (continued)
Label in
Code
Figure 3.10
10
CN30
11
CN35
12
CN5
13
CN190
14
CN18
15
CN16
16
CN25
17
CN8
18
CN55
19
CN6(X1X2,PQE)
20
CN2(D1D2)
21
CN10(M1M2)
22
CN99
Notes:
1.
Standard: The model has this function, the customers can connect corresponding device through this port, such as water pump and hotel key card etc.
Customized: This function needs to be customized before leaving the factory.
Reserved: This port can not be used.
2.
When repairing, PQ connects after-sales tooling
3.
PQ and M1M2 communication ports both are used for indoor and outdoor communication, and only one of them can be used at a tim e. Meanwhile, be
sure to connect the same communication ports (PQ to PQ; M1M2 to M1M2) in case of damage of the main control board.
4.
D1D2 communication ports are used for group control communication. When connecting the group controller, the D1D2 port of the indoor units that are
to be group controlled must be connected in daisy chain, and the group controller must be connected to the X1X2 port of one of the indoor units in the
group control, and set to group control mode. In addition, D1D2 communication ports can also be connected to the central controller.
5.
Refer to Table 3.2 for voltage test instructions of some ports.
Content
Display Panel connection
Humidity sensor connection
Water level port
Drainage pump port
Switch Board
Reserved
Program burning port(indoor unit)
EEV drive port
Remote control ON/OFF port
X1 X2 communication port(with wire controller);
P Q communication port(with ODU by RS-485)
D1 D2 communication port(with Central controller)
M1 M2 communication port(with ODU by HyperLink)
After-sale Kit communication port
Port voltage
Note
[5]
12V DC
Standard
3.3V DC
[5]
Standard
3.3V DC
[5]
Standard
[5]
12V DC
Standard
[5]
5V/12V DC
Standard
3.3V DC
Reserved
[5]
3.3V DC
Standard
12V DC
[5]
Standard
Note 5
Standard
X1 X2:18V DC ;
P,E or Q,E:
Standard
2.5-2.7V DC
D1,E or D2,E
Standard
2.5 - 2.7V DC
24V DC
Standard
[5]
12V DC
Standard