Sinclair SDV 6 Service Manual page 35

Full dc inverter systems

Advertisement

Table 4.2: Indoor unit Parameter Settings
Parameter
Parameter Name
Code
N00
Static pressure of IDU
Power failure memory
N01
function setting for the
IDU
Whether the display
N04
board of IDU receives
remote control signals
N05
Buzzer of the IDU rings
Light (display panel)
N06
setting
N07
Temperature unit
Mode changeover time
N08
interval in the auto mode
(min)
Set outdoor temperature
N11
value when auxiliary
heater is on
Indoor temperature when
N12
auxiliary heater is on
T1 temperature
N13
difference when auxiliary
heater is on
T1 temperature
N14
difference when auxiliary
heater is off
Auxiliary heater used
N15
alone
N16
Auxiliary heater on/off
IDU cold draft prevention
N17
temperature settings
32
Parameter
Default
Range
Value
IDU static
pressure level:
00/01/02/03/
FF
04/05/06/07/08/
09/~/19/FF
00/01
01
00/01
00
00/01/02
02
00/01
01
00/01
00
00/01/02/03
00
-25°C to 20°C
0°C
10°C to 30°C
24°C
0-7
3
0-10
5
00/01
00
00/01/02
00
00/01/02/03/04
00
Remarks
The IDU sets the selected corresponding static pressure
(FF-there may be different default values for different series
of indoor units)
00: None
01: Available
00: Yes
01: No
00: No
01: Yes
02: remote controller only
00: Off
01: On
00: Celsius
01: Fahrenheit
00: 15min
01: 30min
02: 60min
03: 90min
Note: The values are accurate to 1°C or 1°F.
°F: (-13)~68°F
(Accuracy is 1°C)
0-7 indicates 0 - 7°C (Accuracy is 1°C)
0-10 indicates -4 - 6°C (Accuracy is 1°C)
00: No
01: Yes
00: Auto
01: Forced on
02: Forced off
0: 15, 01: 20, 02: 24, 03: 26, 04: anti-cold wind invalid