Full dc inverter systems

Advertisement

Table 7.1: Error code(continues)
Error
code
The built-in room temperature sensor of the wired
E31
controller short-circuits or cuts off
The wireless temperature sensor short-circuits or cuts
E32
off
The external room temperature sensor short-circuits
E33
or cuts off
Tcp (pre-cooled fresh air temperature sensor)
E61
short-circuits or cuts off
Tph (pre-heated fresh air temperature sensor)
E62
short-circuits or cuts off
TA (outlet air temperature sensor) short-circuits or
E81
cuts off
EA1
Outlet air humidity sensor fault
EA2
Return air humidity sensor fault
EA3
Upper wet bulb sensor fault
EA4
Lower wet bulb sensor fault
EC1
R32 refrigerant leakage sensor fault
T2A (heat exchanger liquid pipe temperature sensor)
F01
short-circuits or cuts off
T2 (heat exchanger middle temperature sensor)
F11
short-circuits or cuts off
T2 (heat exchanger middle temperature sensor) over
F12
temperature protection
T2B (heat exchanger gas pipe temperature sensor)
F21
short-circuits or cuts off
P71
Main control board EEPROM fault
P72
IDU display control board EEPROM fault
P31/P34
Fan drive board AC side overcurrent protection
P52
The voltage of the power supply is too low
7.2 Operating Status Codes
Table 7.2:Operating Status Codes
Code
d0
Oil return or preheating operation
dC
Self-cleaning
dd
Mode conflict
dF
Defrosting
d51
Static pressure detection
54
Content
Content
Error
code
U01
Locked (electronic lock)
U11
Unit model code not set
U12
Capacity(HP) code not set
U14
Capacity(HP) code setting error
U15
AHU Kit fan control input signal DIP setting error
Mismatch between indoor unit model and outdoor unit
U26
model
U38
Address code not detected
J01
Motor failed more than once
J1E
IPM (fan module) overcurrent protection
J11
Instantaneous overcurrent protection for phase current
J3E
Low bus voltage fault
J31
High bus voltage fault
J43
Phase current sample bias error
J45
Motor and IDU are unmatched
J47
IPM and IDU are unmatched
J5E
Motor startup failure
J52
Motor blocking protection
J55
Speed control mode setting error
J6E
Phase lack protection of motor
Code
d61
Remote shutdown
d71
IDU backup operation
d72
ODU backup operation
OTA
Main control program upgrading
dH
Hot water mode(Specific series)
Content
Content