Sinclair SDV 6 Service Manual page 98

Full dc inverter systems

Advertisement

8.1.29 d16 - Air inlet temperature of IDU is too low in heating mode
Error display
Error impact
Error trigger
Error recovery
Possible cause
Troubleshooting
Digital display
The faulty IDU stops. Other IDUs of the same system: operate normally.
ODU of the same system: operate normally.
If the air inlet temperature of the IDU is lower than the set value (See the operating temperature
range set out in the IDU Manual) for 5 min in heating mode
Automatic recovery
See the Troubleshooting section.
d16
Note:
1. The inlet air temperature sensor is commonly found in the fresh air IDUs (The sensor code is
defined as T0), and its resistance and temperature characteristics are similar to T1 - return air
temperature sensor. Please refer to the Table of Temperature Sensor Resistance Characteristics
listed in the Maintenance Manual to learn more about the sensor's features.
Panel, display box, and wired controller
Cause 1: Spo t ch eck th e in let air
temperature and measure the
inle t air tempe rature. If th e p oint
check result is th e same as the
measured result (erro r
1° C), it
is a nor ma l pr ote ction measure
for the uni t. Otherwise, refer to
cause 2/3/4
Cause 2: Remove the plug of the
inle t air tempe rature sen sor from
the ma in control boa rd o f th e
IDU, measure its resistan ce
value, and compare it with the
Table of S ensor Resista nce -
Temperature Characteristics (1).
If th e tempera ture that
correspon ds to the resistan ce
value deviates from the actual
inle t air tempe rature by more
than 5° C, the sen sor is
damag ed.
Cause 3: The se nso r bo dy
comes into co nta ct with a cold
source, such as low-temperature
conden sed water and cold
surface of a h eat exchange r,
which cau ses the de tected val ue
to b e lo we r than the normal va lue
Cause 4: If th e e rror ca nnot be
cleared after cau ses 1/2/3 have
bee n e limi nated, the ma in control
boa rd o f th e IDU is d amaged
Display position
It is a normal pro tection
measure fo r the IDU.
When the inlet ai r
temperature exce eds the
set value, the fau lt will b e
cleared
Replace th e in let air
temperature sensor
Elimina te the inte rfer ence
of e xterna l cold source to
the sen sor
Replace th e main control
boa rd o f th e IDU