Sinclair SDV 6 Service Manual page 37

Full dc inverter systems

Advertisement

Table 4.2: Indoor unit Parameter Settings(continues)
Parameter
Parameter Name
Code
IDU cooling mode
N26
temperature
compensation
Maximum indoor
N27
temperature drop in dry
mode
Constant air flow
N30
setting
N31
High ceiling setting
Q4/Q4C air outlet 1
N32
setting
Q4/Q4C air outlet 2
N33
setting
Q4/Q4C air outlet 3
N34
setting
Q4/Q4C air outlet 4
N35
setting
N36
Cooling only for IDU
One-to-more of wired
N37
controller enabled
Long-distance on/off
N38
function setting
Delay time setting (Using
N39
long-distance on/off port
to turn off the IDU)
34
Parameter
Default
Range
Value
00/01/02/03/04
00
00/01/02/03/04
01
00/01
01
00/01/02
00
00/01
00
00/01
00
00/01
00
00/01
00
00/01
00
00/01
00
00/01
00
00/01/.../06
00
Remarks
00: 0°C
01: 1°C
02: 2°C
03: 3°C
04: -1°C
00: 03°C
01: 04°C
02: 05°C
03: 06°C
04: 07°C
00: Constant speed
01: Constant air flow
Set IDU height,
00: 3m
01: 4m
02: 4.5m
00 - Free control
01 - Off
00 - Free control
01 - Off
00 - Free control
01 - Off
00 - Free control
01 - Off
00: Cooling and heating
01: Cooling only
00: No
01: Yes
00: Turn off the IDU when closed
01: Turn off the IDU when open
Note: When turn off the IDU by long-distance on/off port,
the wired controller will display "d61"
00 - No delay
01 - 1min delay
02 - 2min
03- 3min
04- 4min
05- 5min
06- 10min