4/12
Field settings table
Breadcrumb Field code
Setting name
Space heating / cooling
4.9
[F-00]
Pump outside range
4.A
[D-03]
Increase around 0°C
4.B
[9-04]
Overshoot
4.C
[2-06]
Antifrost
Tank
5.2
[6-0A]
Comfort setpoint
5.3
[6-0B]
Eco setpoint
5.4
[6-0C]
Reheat setpoint
5.6
[6-0D]
Heat up mode
└─ Disinfection
5.7.1
[2-01]
Activation
5.7.2
[2-00]
Operation day
5.7.3
[2-02]
Start time
5.7.4
[2-03]
Tank setpoint
5.7.5
[2-04]
Duration
Tank
5.8
[6-0E]
Maximum
5.9
[6-00]
Hysteresis
5.A
[6-08]
Hysteresis
5.B
Setpoint mode
└─ WD curve
5.C
[0-0B]
Leaving water value for high ambient temp. for DHW WD curve.
5.C
[0-0C]
Leaving water value for low ambient temp. for DHW WD curve.
5.C
[0-0D]
High ambient temp. for DHW WD curve.
5.C
[0-0E]
Low ambient temp. for DHW WD curve.
Tank
5.D
[6-01]
Margin
5.E
WD curve type
User settings
└─ Quiet
7.4.1
Mode
7.4.3
Level
└─ Electricity price
7.5.1
High
7.5.2
Medium
7.5.3
Low
User settings
7.6
Gas price
Installer settings
└─ Configuration wizard
└─ System
9.1.3.2
[E-03]
BUH type
9.1.3.3
[E-05]
Domestic hot water
[E-06]
[E-07]
9.1.3.4
[4-06]
Emergency
 4P717810‐1 ‐ 2022.11
Range, step
Default value
R/W
0: Restricted
1: Allowed
R/W
0: No
1: increase 2°C, span 4°C
2: increase 4°C, span 4°C
3: increase 2°C, span 8°C
4: increase 4°C, span 8°C
R/W
1~4°C, step: 1°C
2°C
R/W
0: No
1: Yes
R/W
30~[6-0E]°C, step: 1°C
60°C
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
R/W
0: Reheat only
1: Schedule + reheat
2: Scheduled only
R/W
0: No
1: Yes
R/W
0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
R/W
0~23 hour, step: 1 hour
1
R/W
60°C
R/W
40~60 min, step: 5 min
40 min
R/W
40~65°C, step: 1°C
65°C
R/W
2~40°C, step: 1°C
8°C
R/W
2~20°C, step: 1°C
10°C
R/W
0: Fixed
1: Weather dependent
R/W
35~[6-0E]°C, step: 1°C
55°C
R/W
Min(45,[6-0E])~[6-0E]°C, step: 1°C
60°C
R/W
10~25°C, step: 1°C
15°C
R/W
-40~5°C, step: 1°C
-10°C
R/W
0~10°C, step: 1°C
0°C
R/O
0: 2-points
1: Slope-Offset
R/W
0: OFF
1: Manual
2: Automatic
R/W
0: Quiet
1: More Quiet
2: Most Quiet
R/W
0,00~990/kWh
1/kWh
R/W
0,00~990/kWh
1/kWh
R/W
0,00~990/kWh
1/kWh
R/W
0,00~990/kWh
0,00~290/MBtu
1,0/kWh
R/O
3: 6V (*1)
4: 9W (*2)
R/O
Integrated
R/W
0: Manual
1: Automatic
2: Auto red SH/ DHW ON
3: Auto red SH/ DHW OFF
4: Auto normal SH/ DHW OFF
(*3) Only applicable for models where cooling is possible
Installer setting at variance with
default value
Date
Value
(*1) *6V*_(*2) *9W*_

Advertisement

Table of Contents
loading

Table of Contents