Daikin Altherma 3 R MT F Series Installer's Reference Manual page 58

Table of Contents

Advertisement

7
|
Unit installation
Installer reference guide
58
H
Actual release height:
release
1a 2a
: Without chimney. From floor to top of the unit.
For 180 l units => H
For 230 l units => H
1b 2b
: With chimney. From floor to top of the chimney.
For 180 l units => H
For 230 l units => H
3a
Installation with chimney connected to the outside. The release height
is not relevant. There are no requirements to the minimum floor area.
N/A
Not applicable
Minimum floor area / Release height:
The minimum floor area requirements depend on the release height of the
refrigerant in case of a leakage. The higher the release height, the lower the
minimum floor area requirements.
The default point of release (without chimney) is at the top of the unit. To
decrease the minimum floor area requirements, you can increase the release
height by installing a chimney. If the chimney leads outside of the building, there
are no requirements anymore to the minimum floor area.
You can also take advantage of the floor area of the adjacent room (= room B) by
providing ventilation openings between the two rooms.
For installations in technical rooms (i.e. room that is NEVER occupied by
persons), additionally to patterns 1, 2 and 3, you can also use PATTERN  4. For
this pattern there are no requirements to the minimum floor area if you provide
2 openings (one at the bottom, one at the top) between the room and the
outside to ensure natural ventilation. The room must be protected from frost.
WARNING
Chimney connection. When connecting a chimney, take the following into account:
Unit's connection point for the chimney = 1" male thread. Use a compatible
counterpart for the chimney.
Make sure the connection is airtight.
The chimney material is unimportant.
=1.66 m
release
=1.86 m
release
=1.66 m + Chimney height
release
=1.86 m + Chimney height
release
ERRA08~12E + ELVZ12S18+23E
Daikin Altherma 3 R MT F
4P708478-1 – 2023.05

Advertisement

Table of Contents
loading

Table of Contents