Setting
Setting Name
Number
07
Output Frequency
08
Output Voltage
Inverter Output
09
Power Limit
Inverter Output
10
Power Limit Timer
11
Transfer Mode
975-1175-01-01
Default
Range of Values
Value
60
60
50
120
120
110
108
1.8
0.1 to 1.8
300
1 to 300
APL (appliance),
APL
UPS (UPS)
Adjusting Feature Settings in Configuration Mode
Description
After changing the output frequency setting, turn the unit off
and then on again, in order for the change to take effect.
The wattage setting value can be adjusted by 100-W
increments. Use with Inverter Output Power Limit Timer
especially when pairing with a lithium ion battery. 0.1 is
equivalent to 100 W.
When the range is from 1 to 20, the timer setting value can be
adjusted by 1-s increments. When the range is from 20 to 300,
the timer setting value can be adjusted by 10-s increments.
Use with Inverter Output Power especially when pairing with a
lithium ion battery. The timer is automatically disabled if the
maximum Inverter Output Power limit is selected.
Selecting APL- appliance sets the transfer time from line to
battery to 20 ms. Selecting UPS (uninterruptible power supply)
sets the transfer time from line to battery to 10 ms.
NOTE: Do not connect motor loads when in UPS transfer
mode. See "Troubleshooting".