Overload Conditions; High Surge Loads - Xantrex Freedom XC 1800 Owner's Manual

12vdc inverter charger
Table of Contents

Advertisement

Operating Limits
Operating
Battery
Condition
Voltage
The buzzer sounds a single 1 s low battery alarm
beep and the LCD screen shows error code
Low Voltage
E01. After LBCO Shutdown delay timer runs out,
< LBCO
Shutdown
the unit shuts down inverter output. The buzzer
stops beeping and the LCD screen shows error
code E01.
Instant Low
After 2 s below the limit, the unit shuts down
Voltage
< 10.0 V
inverter output completely. LCD screen turns off
Shutdown
completely.
The display shows error code E02 alternating
with the battery voltage. The red status LED
turns on. 
High Voltage
18.0 V
Shutdown
NOTE: Although the Freedom XC incorporates
over-voltage protection, it can still be damaged if
input voltage exceeds 32.0 VDC.
58
Comment

Overload Conditions

There are two kinds of overload conditions – an overload warning
and an overload shutdown.
Overload
When the Freedom XC's AC load is approximately 100 W
Warning
below the overload shutdown limit of rated watts, the
audible alarm beeps once and the LCD screen shows a
warning code E06.
Overload
When the Freedom XC's AC load increases to near
Shutdown
~1700 W, the audible alarm beeps every 5 s for 1 min
and the LCD screen shows a error code E03. The Status
LED turns solid RED.

High Surge Loads

Some induction motors used in freezers, pumps, and other motor-
operated equipment require high surge currents to start. The
Freedom XC may not be able to start some of these motors even
though their rated steady state current draw is within the
inverter/charger's limits. The unit will shut down and indicate an
overload shutdown.
Freedom XC 1800 (12VDC) Owner's Guide