Display of software version :

The software version is shown by pushing Enter + UP arrow on the upper display
.
Weather-compensated setpoint shifting(climatic regulation):
The RWF55 can be configured so that weather-compensated setpoint shifting is activated when an LG-Ni1000 outside sensor or a
Pt1000 is connected (see parameter InP3).
To take into account the time response of a building, weather-compensated setpoint shifting uses the attenuated outside temperature
rather than the current outside temperature
The minimum and maximum setpoints can be set using the lower setpoint limit SPL and the upper setpoint limit SPH of the menù Crtr.
The system also prevents the lower working range limit oLLo and upper working range limit oLHi from exceeding/dropping below the
system temperature limits.
The heating curve describes the relationship between the boiler temperature setpoint and the outside temperature. It is defined by 2
curve points. For 2 outside temperatures, the user defines the boiler temperature setpoint that is required in each case. The heating
curve for the weather-compensated setpoint is calculated on this basis. The effective boiler temperature setpoint is limited by the upper
setpoint limit SPH and the lower setpoint limit SPL.
For setting climatic regulation function set:
PArA > parametersAt1, Ht1, At2, Ht2
ConF > InP > InP3 parametersSEn3, FnC3 = 1 (Weather-compensated setpoint).