Installing The Burner - Unigas PBY1025 Manual Of Installation - Use - Maintenance

Progressive, fully-modulating heavy oil burners
Table of Contents

Advertisement

INSTALLING THE BURNER

Packing
Burners are despatched in wooden crates whose dimensions are:
2280 mm x 1730 mm x 1360 mm(L x P x H)
Packing cases of this kind are affected by humidity and are not suitable for stacking. The fol-
lowing are placed in each packing case:
burner;
ceramic fibre plait to be inserted between the burner and the boiler;
oil flexible hoses;
oil filter;
oil pump with motor;
envelope containing this manual.
To get rid of the burner's packing, follow the procedures laid down by current laws on disposal of materials.
Handling the burner
ATTENTION! The lhandling operations must be carried out by specialised and trained personnel. If these opera-
tions are not carried out correctly, the residual risk for the burner to overturn and fall down still persists.
To move the burner, use means suitable to support its weight (see paragraph "Technical specifications").
The unpacked burner must be lifted and moved only by means of a fork lift truck.
The burner is mounted on a stirrup provided for handling the burner by means of a fork lift truck: the forks must be inserted into the A
anb B ways. Remove the stirrup only once the burner is installed to the boiler.
Fitting the burner to the boiler
To perform the installation, proceed as follows:
1
drill the furnace plateas decribed in paragraph ("Overall dimensions");
2
place the burner towards the furnace plate: lift and move the burner by means of its eyebolts placed on the top side (see"Lifting and
moving the burner");
3
screw the stud bolts (5) in the plate holes, according to the burner's drilling plate described on paragraph "Overall dimensions";
4
place the ceramic fibre plait on the burner flange;
5
install the burner into the boiler;
6
fix the burner to the stud bolts, by means of the fixing nuts, according to the picture below.
7
After fitting the burner to the boiler, ensure that the gap between the blast tube and the refractory lining is sealed with appropriate
insulating material (ceramic fibre cord or refractory cement).
;
C.I.B. UNIGAS - M039126CE
A
11
H
H
P
P
B
Keys
1
Burner
2
Fixing nut
3
Washer
4
4
Ceramic fibre plait
5
Stud bolt
7
Blast tube
L
L

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pby1030Pby1040

Table of Contents