DANGERS, WARNINGS AND NOTES OF CAUTION THIS MANUAL IS SUPPLIED AS AN INTEGRAL AND ESSENTIAL PART OF THE PRODUCT AND MUST BE DELIVERED TO THE USER. INFORMATION INCLUDED IN THIS SECTION ARE DEDICATED BOTH TO THE USER AND TO PERSONNEL FOLLOWING PRODUCT INSTALLATION AND MAINTENANCE.
3b) FIRING WITH GAS, LIGHT OIL OR OTHER FUELS DIRECTIVES AND STANDARDS Gas burners GENERAL European directives The burner shall be installed by qualified personnel and in compliance -Regulation 2016/426/UE (appliances burning gaseous fuels) with regulations and provisions in force; wrong installation can cause -2014/35/UE (Low Tension Directive) injuries to people and animals, or damage to property, for which the -2014/30/UE (Electromagnetic compatibility Directive)
Burner data plate Type Gas - Light oil burners For the following information, please refer to Model Year European Directives the data plate: S.Number -Regulation 2016/426/UE (appliances burning gaseous fuels) burner type and burner model: must be Output Oil Flow -2014/35/UE (Low Tension Directive) reported in any communication with the Fuel...
Page 5
PART I: SPECIFICATIONS PART I: SPECIFICATIONS BURNERS FEATURES RX75, RX75S, R75R, R75A, R75R P75A ,P75R Note: the figure is indicative only. Control panel with startup switch Gas valves group Electrical panel Air intake Blast tube + Combustion head Flange Adjusting cam (progressive/fully modulating burners only) Air pressure switch Gas operation: the gas coming from the supply line, passes through the valves group provided with filter and stabiliser.
Burners are identified by burner type and model. Burner model identification is described as follows. Type RX75R Model MD. S. BURNER TYPE RX75 - RX75S - RX75R - R75A - R75R - P75A - P75R FUEL M - Natural gas L - LPG B - Biogas C - Town gas...
Page 12
PART I: SPECIFICATIONS How to read the burner “Performance curve” To check if the burner is suitable for the boiler to which it must be instal- Campo di lavoro bruciatori lled, the following parameters are needed: Tipo P60 Mod. M-xx.x.IT.A.0.50 - M-.xx.x.IT.A.0.65 furnace input, in kW or kcal/h (kW = kcal/h/860);...
RX75R RX75 R75R / P75R R75A / P75A To get the input in kcal/h, multiply value in kW by 860. Data are referred to standard conditions: atmospheric pressure at 1013mbar, ambient temperature at 15° C NOTE: The performance curve is a diagram that represents the burner performance in the type approval phase or in the laboratory tests, but does not represent the regulation range of the machine.
Page 14
Gas rate Stm RX75 Gas rate Stm R75R / P75R R75A / P75A Gas rate Stm Gas rate Stm ATTENTION: the gas rate value is quoted on the x-axis, the related network pressure is quoted on the y-axis (pressure value in the combustion chamber is not included). To know the minimum pressure at the gas train inlet, necessary to get the requested gas rate, add the pressure value in the combustion chamber to the value read on the y-axis.
Page 15
PART I: SPECIFICATIONS Pressure in the Network / gas flow rate curves(LPG) R75A L-.. / P75A L-.. Gas rate Stm ATTENTION: the gas rate value is quoted on the x-axis, the related network pressure is quoted on the y-axis (pressure value in the combustion chamber is not included). To know the minimum pressure at the gas train inlet, necessary to get the requested gas rate, add the pressure value in the combustion chamber to the value read on the y-axis.
Page 16
THE USER CAN REFERS TO THE PRESSURE-RATE CURVES AS GENERAL INFORMATION ONLY. Pressure - rate in combustion head curves (natural gas) Curves are referred to pressure = 0 mbar in the combustion chamber! RX75S M-.. RX75R M-.. RX75 M-.. R75R M-.. / P75R M-.. R75A M-.. / P75A M-..
Page 17
PART I: SPECIFICATIONS Pressure - rate in combustion head curves (LPG) Curves are referred to pressure = 0mbar in the combustion chamber! R75A L-.. / P75A L..
Page 18
PART II: INSTALLATION PART II: INSTALLATION MOUNTING AND CONNECTING THE BURNER Transport and storage ATTENTION! The equipment must be installed in compliance with the regulations in force, following the manufac- turer’s instructions, by qualified personnel. All handling operations must be carried out with appropriate resources and qualified personnel ATTENTION: Use intact and correctly dimensioned hoisting equipment, conforms to the local regulations and health and safety regulations.
Page 19
SIDE DOWN Matching the burner to the boiler (R75R - R75A - P75R - P75A) The burners described in this manual have been tested with combustion chambers that comply with EN676 regulation and whose dimensions are described in the diagram . In case the burner must be coupled with boilers with a combustion chamber smaller in diameter or shorter than those described in the diagram, please contact the supplier, to verify that a correct matching is possible, with respect of the application involved.
Page 20
PART II: INSTALLATION Matching the burner to the boiler low NOx burners) (RX75 - RX75S - RX75R) The burners described in this manual have been tested with combustion chambers that comply with EN676 regulation and whose dimensions are described in the diagram . In case the burner must be coupled with boilers with a combustion chamber smaller in dia- meter or shorter than those described in the diagram, please contact the supplier, to verify that a correct matching is possible, with respect of the application involved.
Page 21
PART II: INSTALLATION GAS TRAIN CONNECTIONS The diagrams show the components of the gas trai included in the delivery and which must be fitted by the installer.The diagrams are in compliance with the current laws. Gas train with valves group MB-DLE (2 valves + gas filter + pressure governor) BY OTHERS BY BURNER CONSTRUCTOR GAS INLET...
PART II: INSTALLATION MultiBloc MB-DLE - Assembling the gas train F”direction” arrows for gas supply network installation Keys 1 Gasket 2 Gas filter 3 Gas valves group 4 Bellows unit 41Manual valve MULTIBLOC DUNGS MB-DLE 405..412 Mounting 1. Mount flange onto tube lines: use appropriate sealing agent (see Fig. 9); 2.
Page 23
PART II: INSTALLATION MultiBloc MBE Actuator VD-V Actuator VD-R Gas filter PS pressure Pressure switch PG min sensor Leakage pressure switch Valve body VB Pressure switch PG max Fig. 15Example of gas train MBE To mount the gas train, proceed as follows: 1-a) in case of threaded joints: use proper seals according to the gas used;...
Page 24
PART II: INSTALLATION Mounting VD-R & PS-... Actuator VD-R Actuator VD-V 1. Gas pressure regulation is possible with VD-R and PS pressure sensor only. WARNING!!!!. For US/CN installation, the output pressure must be monitoried by min. and max. pressure switches set to +/- 20% of the setpoint. 2.
Page 25
PART II: INSTALLATION Siemens VGD20.. e VGD40.. Siemens VGD20.. and VGD40.. gas valves - with SKP2.. (pressure governor) - Connect the reference gas pipe (TP in figure; 8mm-external size pipe supplied loose), to the gas pressure nipples placed on the gas pipe, downstream the gas valves: gas pressure must be measured at a distance that must be at least 5 times the pipe size.
Page 26
PART II: INSTALLATION Once the train is installed, connect the gas valves group and pressure switches plugs. Gas Filter (if provided) The gas filters remove the dust particles that are present in the gas, and prevent the elements at risk (e.g.: burner valves, counters and regulators) from becoming rapidly blocked.
PART II: INSTALLATION ELECTRICAL CONNECTIONS WARNING! Respect the basic safety rules. make sure of the connection to the earthing system. do not reverse the phase and neutral connections. fit a differential thermal magnet switch adequate for connection to the mains. WARNING! before executing the electrical connections, pay attention to turn the plant’s switch to OFF and be sure that the burner’s main switch is in 0 position (OFF) too.
PART III: OPERATION PART III: OPERATION LIMITATIONS OF USE THE BURNER IS AN APPLIANCE DESIGNED AND CONSTRUCTED TO OPERATE ONLY AFTER BEING CORRECTLY CONNEC- TED TO A HEAT GENERATOR (E.G. BOILER, HOT AIR GENERATOR, FURNACE, ETC.), ANY OTHER USE IS TO BE CONSIDE- RED IMPROPER AND THEREFORE DANGEROUS.
Page 29
PART III: OPERATION Fig. 20 - Burner front panel Keys Lock-out LED Hi-flame operation LED Lo-flame operation LED “Ignition transformer operation” LED “Fan motor overload tripped” LED “EV2 opening” LED “EV1 opening” LED “Gas pressure switch signal ” LED Gas proving system lockout signalling LED Main switch Reset pushbutton for control box Operation selector MAN - AUTO (operation in manual...
PART III: OPERATION MultiBloc MBE Regulation VD-R whith PS Setting scale is „Not“ linear! Various sensors available. Output pressure according to sensor‘s measuring range. Increasing pressure Adjust the outlet pressure to the value specified by the burner or equipment manufacturer! Decreasing pressure While making outlet pressure adjustments, do not exceed a value that creates a hazardous condition to the...
Page 31
PART III: OPERATION Adjusting the gas valves group Multibloc MB-DLE VS T(VR) The multibloc unit is a compact unit consisting of two valves, gas pressure switch, pres- sure stabilizer and gas filter. The valve is adjusted by means of the RP regulator after slackening the locking screw VB by a number of turns.
Page 32
Adjusting the combustion head CAUTION: perform these adjustments once the burner is turned off and cooled. R75A, R75R, P75A, P75R The burner is factory-adjusted with the combustion head in the "MAX" position, accordingly to the maximum power. To operate the bur- ner at a lower power, progressively shift back the combustion head, towards the "MIN"...
Page 33
PART III: OPERATION (R75A M-..) Center head holes gas flow regulation To adjust the gas flow, partially close the holes, as follows: loosen the three V screws that fix the adjusting plate D; insert a screwdriver on the adjusting plate notches and let it move CW/CCW as to open/close the holes; once the adjustmet is performed, fasten the V screws.
Page 34
PART III: OPERATION Adjusting the gas valves group and removing the filter MULTIBLOC DUNGS MB-DLE 405..412 Check the filter at least once a year! Change the filter if the pressure difference between pressure connection 1 and 3 (Fig. 28-Fig. 29)is p > 10 ...
Page 35
PART III: OPERATION MultiBloc MBE MultiBloc VD Mounting to push position 1. Position VD on VB, fig. 2+3. 2. Slide VD forward up to the stop, fig. 4. 3. Screw VD on with 2 M5 screws for each, max. 5 Nm/44 in.-lb., fig. 5/6. 4.
PART III: OPERATION Adjustment procedure Turn the burner on by means of its main switch S1: if the burner locks (LED B1 on in the control panel) press the RESET button (S2) on the control panel. See chapter “Operation” for further details. check the fan motor rotation Start the burner up by means of the thermostat series and wait unitl the pre-purge phase comes to end and that burner starts up;...
Page 37
PART III: OPERATION Double-stage burners drive the burner to the low flame stage by means of the TAB thermostat; 10 ;In order to change the gas flow rate slacken the nuts DB (Fig. 27) and adjust the opening angle of the gas butterfly valve by rota- ting the rod TG (clockwise rotation increases gas flow, anticlockwise rotation decreases it).
Page 38
PART III: OPERATION Progressive burners Once the procedure till step 8 described on paragraph “” on page 30, is accomplished, go on as follows: set the low flame cam matching the high flame cam; 10 set the TAB thermostat to the minimum in order that the actuator moves progressively towards the low flame position;; The manual air damper control is not provided on these actuators.
Page 39
PART III: OPERATION Calibration air and gas pressure switches The air pressure switch locks the control box if the air pressure is not the one requested. If it happens, unlock the burner by means of the control box unlock pushbutton, placed on the bur- ner control panel.
PART IV: MAINTENANCE PART IV: MAINTENANCE At least once a year carry out the maintenance operations listed below. In the case of seasonal servicing, it is recommended to carry out the maintenance at the end of each heating season; in the case of continuous operation the maintenance is carried out every 6 months.
Page 41
PART IV: MAINTENANCE Adjusting the gas valves group and removing the filter MULTIBLOC DUNGS MB-DLE 405..412 Check the filter at least once a year! Change the filter if the pressure difference between pressure connection 1 and 3 (Fig. 1-Fig. 3)is p > 10 ...
Page 42
PART IV: MAINTENANCE MultiBloc MBE MultiBloc VD Mounting to push position 1. Position VD on VB, fig. 2+3. 2. Slide VD forward up to the stop, fig. 4. 3. Screw VD on with 2 M5 screws for each, max. 5 Nm/44 in.-lb., fig. 5/6. 4.
Page 43
G hole. RX75S 3÷4 the gap between ignition electrode EA and grounded electrode M must be 3 ÷ 4 mm. Ignition electrod must be positioned over the G hole. ER - Detection electrode EA - Ignition electrode R75A, P75A...
Reassemble the burner by fllowing the procedure in the reversed order. Detection electrode RX75, RX75S, RX75R R75A . P75A Detection electrode R75R, P75R WIRING DIAGRAMS Refer to the attached wiring diagrams.
PART IV: MAINTENANCE Checking the detection current with electrode (natural gas) To check the detection signal follow the scheme in the picture below. If the signal is less than the value indicated, check the position of the detection electrode or detector, the electrical contacts and, if necessary, replace the electrode or the detector. Connector LME: 1 LGK: 24...
Page 46
PART IV: MAINTENANCE TROUBLESHOOTNG GUIDE - Gas operation * No electric power supply * Wait until power supply is back * Main switch open * Close the switch * Thermostats open * Check set points and thermostat connections * Bad thermostat set point or broken thermostat * Set or replace the thermostat * No gas pressure * Restore gas pressure...
Page 48
BOARD IGNITION CABLE 1.1.1 BOARD GAS MANIFOLD 1.1.2 CONTROL BOX SOCKET DETECTION ELECTRODE 1.1.3 IGNITION TRANSFORMER STANDARD COMBUSTION HEAD 1.1.4 PRINTED CIRCUIT BOARD O RING 1.1.5.1 FRONT CONTROL PANEL 6.5.1 NOZZLE HOLDER 1.1.5.2 LIGHT 6.5.2 IGNITION ELECTRODE 1.1.5.3 LIGHT AIR INTAKE 1.1.5.4 FLAME UNLOCK BUTTON AIR PRESSURE SWITCH...
APPENDIX SIEMENS LME11/21/22 CONTROL BOX The series of equipment LME.. is used for the starup and supervisione of 1- or 2- stage gas burners. The series LME.. is interchangeable with the series LGB.. and LMG.., all diagrams and accessories are interchangea- START-UP PROGRAM ble.
Page 50
LME11 control sequence LME21 control sequence B´ B´ SB / R SB / R W / GP W / GP (LR) BV2 7101d05/0206 Control sequence Waiting time LME22 control sequence Purge time B´ TSA Ignition safety time SB / R Preignition time W / GP Postignition time...
Page 51
LME11 connection diagram Connection diagram Error message (alarm) Fuel valve PC control EK2 Remote lockout reset button RESET Flame signal Gas pressure switch Air pressure switch Load controller K2/1 K2/2 Fan motor Control thermostat/pressurestat Safety limit thermostat R / W Limit thermostat /pressure switch Ignition transformer 7101 24 /0606...
Page 52
CONTROL PROGRAM IN THE EVENT OF FAULT CONTROL BOX LOCKED If a fault occurs, all outputs will immediately be deactivated (in less In the event of lockout, the LME.. remains locked and the red signal lamp than 1s). (LED) will light up.The burner control can immediately be reset. This state After an interruption of power, a restart will be made with the full pro- is also mantained in the case fo mains failure.
Page 56
C.I.B. UNIGAS S.p.A. Via L.Galvani, 9 - 35011 Campodarsego (PD) - ITALY Tel. +39 049 9200944 - Fax +39 049 9200945/9201269 web site: www.cibunigas.it - e-mail: cibunigas@cibunigas.it Note: specifications and data subject to change. Errors and omissions excepted.
Page 57
MANUAL FOR OPERATION AND CALIBRATION MODULATOR SIEMENS RWF 40…. M12905CH Rev. 07 11/09...
INSTRUMENT MOUNTING Mount the instrument using the relevant mounts as illustrated in the figure. To wire the instrument and sensors, follow the instructions given on the burner's wiring diagrams. INSTRUMENT FRONTAL PANEL Current value or value of parameter (red) Setpoint or name of parameter (green) Manual operation...
INSTRUMENT SETTINGS The instrument comes with a number of factory settings that are good for 90% of cases. However, you can set or edit parame- ters proceeding as follows 1. Setting or editing of setpoint value With the burner switched off (thermostat/pressure switch series contacts open, i.e. terminals 3-4 open), press the PGM key, holding it down for less than 2 sec..
Page 60
SCL2:lower limit for analogue input 2 (same as SCL but for input 2 - factory setting 0); SCH2:upper limit for analogue input 2 (same as SCH but for input 2 - factory setting 100); SPL: lower setpoint limit (same as SCL but for setpoint - factory setting 0); SPH: upper setpoint limit (same as SCH but for setpoint - factory setting 100);...
Page 61
TABLE 1 - "PID" PARAMETERS AND RELEVANT FACTORY SETTINGS Parameter Display Values range Factory setting Remarks Limit value for auxiliary from -1999 to 9999 Do not alter contact (*) digit Auxiliary contact switching HYST from 0 to 999.9 digit Do not alter differential (*) from 0.1 to 9999 Proportional band (*)
Page 63
TABLE 3 - CONFIGURATION C112 Red display 1^ digit 2^ digit 3^ digit 4^ digit Auxiliary limit switch K6 none lk1 function for input 1 lk2 function for input 1 lk3 function for input 1 lk4 function for input 1 lk5 function for input 1 lk6 function for input1 lk7 function for input 1...
Page 64
TABLE 4 - CONFIGURATION C113 Red display 1^ digit 2^ digit 3^ digit 4^ digit Instrument addresses (for RWF 40.003 only address 0 address 1 address... address 99 Unit of measurement and decimal place °C without decimal °C and 1 decimal °F without decimal °F and 1 decimal Activation of “K6”...
Page 66
Probe electric connection : With 7 pins connector version With terminals version TRASDUCER PASSIVE TRASDUCER PASSIVE CONNECTION ONLY CONNECTION ONLY TRASDUCER PASSIVE TRASDUCER PASSIVE CONNECTION ONLY CONNECTION ONLY...
Page 67
With external setpoint C111 configuration code = X1X1 With setpoint modified by independent management system C111 configuration code = X9XX SCH2= 0.5x (SPH - SPL) SCL2= -0.5 x (SPH - SPL) Example: SPH= max. 130° C SPL= min. 30° C SCH2= 0.5 x (130 - 30) = 50 SCL2= -0.5 x (130 - 30) = -50...
Page 68
APPENDIX: PROBES CONNECTION To assure the utmost comfort, the control system needs reliable information, which can be obtained provided the sensors have been installed correctly. Sensors measure and transmit all variations encountered at their location. Measurement is taken based on design features (time constant) and according to specific operating conditions. With wiring run in raceways, the sheath (or pipe) containing the wires must be plugged at the sensor's terminal board so that currents of air cannot affect the sensor's measurements Ambient probes (or ambient thermostats)
Page 69
Duct or pipe sensors Installing pressure sensors Installing temperature sensors A - installation on ducts carrying fluids at max. temperature For measuring outlet air: 80°C B - installation on ducts at temperature over 80°C and for refri- after delivery fan or gerants after coil to be controlled, at a distance of at least 0,5 m C - installation on ducts at high temperatures:...
Page 70
Immersion or strap-on sensors Immersion probes mounting Sensors must be installed on the stretch of pipe in which fluid circulates all the time. The rigid stem (sensing element doing the measuring) must be inserted by at least 75mm and must face the direction of flow.
Page 71
Duct pressure switches and sensors Installing differential pressure probes for air Basic principles Measuring static pressure (i.e. pressure exerted by air on pipe walls) A - Control a filter (clogging) Measuring dinamic pressure B - Control a fan (upstream/downstream) kg/m3, specific weight of air m/s, air speed 9.81 m/s2, gravity acceleration mm C.A., dynamic pressure...
Page 72
Spare parts Description Code Modulator RWF40.000 2570112 Adapting frame Siemens ARG40 from RWF32.. to RWF40.. 2570113 Temperature probe Siemens QAE2120.010A (30÷130°C) 2560101 Temperature probe Siemens QAM2120.040 (-15÷+50°C) 2560135 Thermoresistor Pt1000 ø = 6mm L = 100mm (30÷130°C) 2560188 Thermoresistor Pt1000 ø = 10mm L = 200mm (0÷350°C) 2560103 Pressure probe Siemens QBE2..