Page 2
NOTICES THIS MANUAL IS SUPPLIED AS AN INTEGRAL AND ESSENTIAL PART OF THE PRODUCT AND MUST BE DELIVERED TO THE USER. INFORMATION INCLUDED IN THIS SECTION ARE DEDICATED BOTH TO THE USER AND TO PERSONNEL FOLLOWING PRODUCT INSTALLATION AND MAINTENANCE. THE USER WILL FIND FURTHER INFORMATION ABOUT OPERATING AND USE RESTRICTIONS, IN THE SECOND SEC- TION OF THIS MANUAL.
Page 3
3b) FIRING WITH GAS, LIGHT OIL OR OTHER FUELS GENERAL INSTRUCTIONS DEPENDING ON FUEL USED GENERAL The burner shall be installed by qualified personnel and in 3a) ELECTRICAL CONNECTION compliance with regulations and provisions in force; wrong For safety reasons the unit must be efficiently earthed and installation can cause injuries to people and animals, or installed as required by current safety regulations.
Page 4
PART I: INSTALLATION MANUAL SPECIFICATIONS BURNER TYPE G18 SP PG25 SP PG30 TN Output min. kcal/h 90.300 140.200 140.200 max. kcal/h 180.000 250.200 300.000 min. kW max. kW Oil rate kg/h min. kg/h max. Fuel Light oil Light oil Light oil...
Page 7
To get rid of the burner’s packing and in the event of scrapping of the latter, follow the procedures laid down by current laws on disposal of materials G18 SP Fitting the burner to the boiler Fix the flange of the burner to the boiler as shown in Fig. 6.
Page 8
Electrical wiring G18 SP PG25 SP PG30 TN Fig. 8a Fig. 8b Fig. 8c Remove the burner’s cover; Remove the cover of the electrical board fitted on the burner. effect the connections to the supply Effect the connections to the supply terminal board following the diagrams in Fig.
Page 9
18 bar, by means of the regulation screw. PG30 TN Set the pump to a pressure value from 10 to 14 bar, depending by the nozzle fitted (see Tab. 2). Tab. 1 - Burners G18 SP - PG25 SP Pressure (bar) 1.75 6.02...
Page 10
LIGHT OIL PUMPS Pump Suntec AS57 C Viscosity range 2 - 12 mm²/s (cSt) Oil temperature 0 - 60°C into the pump. Inlet pressure 2 bar max. Return pressure 2 bar max. Suction height max. 0,45 bar to avoid air separation from oil.
Page 11
AIR RATE SETTING G18 SP Loose the screw VBS and rotate the air damper in the desired position, to set the air flow. At the end of settings, tight the screw VBS. Fig. 13 PG25 SP - PG30 TN Loose the screw VBS and set the air flow, working directly on the air damper.
Page 12
PART II: OPERATION MANUAL LIMITATIONS OF USE THE BURNER IS AN APPLIANCE DESIGNED AND CONSTRUCTED TO OPERATE ONLY AFTER BEING CORRECTLY CONNECTED TO A HEAT GENERATOR (E.G. BOILER, HOT AIR GENERATOR, FURNACE, ETC.), ANY OTHER USE IS TO BE CONSIDERED IMPROPER AND THEREFORE DANGEROUS. THE USER MUST GUARANTEE THE CORRECT FITTING OF THE APPLIANCE, ENTRUSTING THE INSTALLATION OF IT TO QUALIFIED PERSONNEL AND HAVING THE FIRST COMMISSIONING OF IT CARRIED OUT BY A SERVICE CENTRE AUTHORISED BY THE COMPANY MANUFACTURING THE BURNER.
Page 13
Examine and carefully clean the flame detector cell and replace if necessary. If in doubt light the burner and check the detector circuit as shown in Fig. 19. Correct posiotion of electrodes and combustion head - G18 SP Prepare a stable surface where lying the burner during maintenance.
Page 14
Correct posiotion of electrodes and combustion head Fig. 18 Tab. 3 Mod. G18 SP PG25 SP 8 mm 4 mm 5,5-6,5 mm 8-10 mm PG30 TN CHECK OF THE IONIZATION CURRENT FLAME CONTROLLER To check the detector signal follow the prcedure shown in Fig.
LANDIS OIL BURNERS AUTOMATIC CONTROLLER LOA24 Wiring diagram of the programme To ensure correct wiring it is essential to observe local standards and follow the instructions of the burner manufacturer with regard to LOA... safety devices are intended for use solely with QRB... photore- assembly and start-up.
Page 24
Technical characteristics Commands in the event of operational interference Voltage 220V -15%..240V+10% or Stray light/premature ignition 100V -15%...110V+10% During pre-purge and/or pre-ignition there should be no flamesignal. If Frequency 50...60Hz +/- 6% there is a flame signal, eg from premature ignition due to a faulty sole- External fuse max.10A slow action noid, external light, short circuit in the photoresisto or wiring, malfunc-...
SUNTEC PUMPS AS 47 - 57 - 67 Operating principle The gear set draws oil from the tank through the built-in filter and transfers it to the valve that regulates the oil pressure to the nozzle line. All oil that does not go through the nozzle line will be dumped through the valve back to the return line in two pipe installation or, if it is a one-pipe installation, back to suction port in the gear set .
DELTA VM PUMPS In the VM series of DELTA pumps the pressurised flow of oil P is shut off by a built in solenoid and may therefore be switched on for startup of the motor pre-purge) or off before the motor itself switches off (flame goes out instantly when the spray from the nozzle stops). Oil pressure is regulated and kept constant by the piston valve which is activated when the light comes on to signify that the oil discharged exce- eds nozzle capacity and is being returned to the tank (twin-pipe system) or being returned to the suction pipe through a bypass in the pipe (sin- gle-pipe system).
SUNTEC AT2 PUMP The SUNTEC AT2 oil pump features 2 mode pressure operation and incorporates a blocking solenoid valve with in-line cut-off function. Switching between low and high modes is assured by a 2nd integral solenoid valve. Operation The gear set draws oil from the tank through the built-in filter and transfers it to the nozzle line via the cut-off solenoid valve. Pressure regulation is assured by two spool valves, one for each pressure mode.
NOTES FOR USE AND MAINTENANCE OF FUEL PUMPS Make sure that the by-pass plug is not used in a single pipe installation, because the fuel unit will not function properly and damage to the pump and burner motor could result. Do not use fuel with additives to avoid the possible formation over time of compounds which may deposit between the gear teeth, thus obstructing them.