MANUAL OF
INSTALLATION
OPERATION
MAINTENANCE
LIGHT OIL BURNERS
G18 SP
PG25 SP
PG30 TN
M03978AA Rev. 0 05/04
Complying with
EMC 79/336/CEE
LV 73/23/CEE
Documentazione Tecnica CIB Unigas - Campodarsego (PD)

Advertisement

loading

Summary of Contents for Unigas G18 SP

  • Page 1 MANUAL OF INSTALLATION OPERATION MAINTENANCE LIGHT OIL BURNERS G18 SP PG25 SP PG30 TN M03978AA Rev. 0 05/04 Complying with EMC 79/336/CEE LV 73/23/CEE Documentazione Tecnica CIB Unigas - Campodarsego (PD)
  • Page 2 NOTICES THIS MANUAL IS SUPPLIED AS AN INTEGRAL AND ESSENTIAL PART OF THE PRODUCT AND MUST BE DELIVERED TO THE USER. INFORMATION INCLUDED IN THIS SECTION ARE DEDICATED BOTH TO THE USER AND TO PERSONNEL FOLLOWING PRODUCT INSTALLATION AND MAINTENANCE. THE USER WILL FIND FURTHER INFORMATION ABOUT OPERATING AND USE RESTRICTIONS, IN THE SECOND SEC- TION OF THIS MANUAL.
  • Page 3 3b) FIRING WITH GAS, LIGHT OIL OR OTHER FUELS GENERAL INSTRUCTIONS DEPENDING ON FUEL USED GENERAL The burner shall be installed by qualified personnel and in 3a) ELECTRICAL CONNECTION compliance with regulations and provisions in force; wrong For safety reasons the unit must be efficiently earthed and installation can cause injuries to people and animals, or installed as required by current safety regulations.
  • Page 4 PART I: INSTALLATION MANUAL SPECIFICATIONS BURNER TYPE G18 SP PG25 SP PG30 TN Output min. kcal/h 90.300 140.200 140.200 max. kcal/h 180.000 250.200 300.000 min. kW max. kW Oil rate kg/h min. kg/h max. Fuel Light oil Light oil Light oil...
  • Page 5 OVERALL DIMENSIONS Fig. 1 G18SP 121÷134 Fig. 2 PG25 SP PG30 TN PART I: INSTALLATION MANUAL...
  • Page 6 PERFORMANCE CURVES G18 SP Fig. 3 PG25 SP Fig. 4 -0,5 PG30 TN Fig. 5 -0,5 -1,5 140 160 180 200 220 240 260 280 300 320 340 360 380 PART I: INSTALLATION MANUAL...
  • Page 7 To get rid of the burner’s packing and in the event of scrapping of the latter, follow the procedures laid down by current laws on disposal of materials G18 SP Fitting the burner to the boiler Fix the flange of the burner to the boiler as shown in Fig. 6.
  • Page 8 Electrical wiring G18 SP PG25 SP PG30 TN Fig. 8a Fig. 8b Fig. 8c Remove the burner’s cover; Remove the cover of the electrical board fitted on the burner. effect the connections to the supply Effect the connections to the supply terminal board following the diagrams in Fig.
  • Page 9 18 bar, by means of the regulation screw. PG30 TN Set the pump to a pressure value from 10 to 14 bar, depending by the nozzle fitted (see Tab. 2). Tab. 1 - Burners G18 SP - PG25 SP Pressure (bar) 1.75 6.02...
  • Page 10 LIGHT OIL PUMPS Pump Suntec AS57 C Viscosity range 2 - 12 mm²/s (cSt) Oil temperature 0 - 60°C into the pump. Inlet pressure 2 bar max. Return pressure 2 bar max. Suction height max. 0,45 bar to avoid air separation from oil.
  • Page 11 AIR RATE SETTING G18 SP Loose the screw VBS and rotate the air damper in the desired position, to set the air flow. At the end of settings, tight the screw VBS. Fig. 13 PG25 SP - PG30 TN Loose the screw VBS and set the air flow, working directly on the air damper.
  • Page 12 PART II: OPERATION MANUAL LIMITATIONS OF USE THE BURNER IS AN APPLIANCE DESIGNED AND CONSTRUCTED TO OPERATE ONLY AFTER BEING CORRECTLY CONNECTED TO A HEAT GENERATOR (E.G. BOILER, HOT AIR GENERATOR, FURNACE, ETC.), ANY OTHER USE IS TO BE CONSIDERED IMPROPER AND THEREFORE DANGEROUS. THE USER MUST GUARANTEE THE CORRECT FITTING OF THE APPLIANCE, ENTRUSTING THE INSTALLATION OF IT TO QUALIFIED PERSONNEL AND HAVING THE FIRST COMMISSIONING OF IT CARRIED OUT BY A SERVICE CENTRE AUTHORISED BY THE COMPANY MANUFACTURING THE BURNER.
  • Page 13 Examine and carefully clean the flame detector cell and replace if necessary. If in doubt light the burner and check the detector circuit as shown in Fig. 19. Correct posiotion of electrodes and combustion head - G18 SP Prepare a stable surface where lying the burner during maintenance.
  • Page 14 Correct posiotion of electrodes and combustion head Fig. 18 Tab. 3 Mod. G18 SP PG25 SP 8 mm 4 mm 5,5-6,5 mm 8-10 mm PG30 TN CHECK OF THE IONIZATION CURRENT FLAME CONTROLLER To check the detector signal follow the prcedure shown in Fig.
  • Page 15 ELECTRICAL DIAGRAMS Electrical diagram cod. 01-369 Rev. 1 - Burners G18 SP Time counter EVG1 Light oil solenoid valve Ist stage EVG2 Light oil solenoid valve IInd stage Fuse Photoresistor Main switch Phase Burner operation light Burner lockout light LOA24/BOA64...
  • Page 16 Electrical diagram cod. 04-575 - Burners PG25 SP Legenda Time counter EVG1 Light oil solenoid valve Ist stage EVG2 Light oil solenoid valve IInd stage Fuse Photoresistor Main switch Phase Burner lockout light LEVG1 Opening of EVG1 signalization light LEVG2 Opening of EVG2 signalization light Burner operation signalization light LOA24/BHO64...
  • Page 17 Electrical diagram cod. 04-574 - Burner PG30 TN EVG1 Light oil solenoid valve Fuses Photoresistor Main switch Phase Burner lockout light LEVG1 EVG1 opening signalization light Burner operation light LOA24/BHO64 Flame monitor device Ignition transformer light Power supply terminal block Terminal block for burner components connection Fan motor Neutral...
  • Page 18 SPARE PARTS Burner G18 SP PART III: MAINTENANCE MANUAL...
  • Page 19 G18 SP POS. DESCRIPTION CODE 301.00.19 HOUSING CONDENSER 603.00.04 MOTOR 218.00.09 202.04.45 FLAME CONTROL DEVICE LOA24 SOCKET FOR LOA24 203.04.09 SUPPORT BRACKET 243.00.04 217.01.06 TRANSFORMER 205.02.28 BURNER CASING 215.00.04 COMPLETE JOINT 302.00.20 ATOMIZER NOZZLE 261... ATOMIZER SUPPORT 228.00.06 201.01.02 BOTTOM 605.01.22...
  • Page 20 Burners PG25 SP - PG30 TN PART III: MAINTENANCE MANUAL...
  • Page 21 PG25 SP PG30 TN POS. DESCRIPTION ELECTRIC BOARD 610.00.86 610.00.86 SOCKET FOR FLAME CONTROL DEVICE 203.04.15 203.04.15 FLAME CONTROL DEVICE 202.04.45 202.04.45 IGNITION TRANSFORMER 217.01.07 217.01.07 TOP COVER 221.01.03 221.01.03 LANDIS PHOTORESISTOR 251.00.03 251.00.03 GASKET 211.00.04 211.00.04 IGNITION CABLES 605.01.09 605.01.09 SHORT ELECTRODE 208.02.08...
  • Page 22: Table Of Contents

    APPENDICX: COMPONENTS CHARACTERISTICS LANDIS OIL BURNERS AUTOMATIC CONTROLLER LOA24 SUNTEC PUMPS AS 47 - 57 - 67 DELTA VM PUMPS SUNTEC AT2 PUMP NOTES FOR USE AND MAINTENANCE OF FUEL PUMPS APPENDICX: COMPONENTS CHARACTERISTICS...
  • Page 23: Landis Oil Burners Automatic Controller Loa24

    LANDIS OIL BURNERS AUTOMATIC CONTROLLER LOA24 Wiring diagram of the programme To ensure correct wiring it is essential to observe local standards and follow the instructions of the burner manufacturer with regard to LOA... safety devices are intended for use solely with QRB... photore- assembly and start-up.
  • Page 24 Technical characteristics Commands in the event of operational interference Voltage 220V -15%..240V+10% or Stray light/premature ignition 100V -15%...110V+10% During pre-purge and/or pre-ignition there should be no flamesignal. If Frequency 50...60Hz +/- 6% there is a flame signal, eg from premature ignition due to a faulty sole- External fuse max.10A slow action noid, external light, short circuit in the photoresisto or wiring, malfunc-...
  • Page 25: Suntec Pumps As 47

    SUNTEC PUMPS AS 47 - 57 - 67 Operating principle The gear set draws oil from the tank through the built-in filter and transfers it to the valve that regulates the oil pressure to the nozzle line. All oil that does not go through the nozzle line will be dumped through the valve back to the return line in two pipe installation or, if it is a one-pipe installation, back to suction port in the gear set .
  • Page 26: Delta Vm Pumps

    DELTA VM PUMPS In the VM series of DELTA pumps the pressurised flow of oil P is shut off by a built in solenoid and may therefore be switched on for startup of the motor pre-purge) or off before the motor itself switches off (flame goes out instantly when the spray from the nozzle stops). Oil pressure is regulated and kept constant by the piston valve which is activated when the light comes on to signify that the oil discharged exce- eds nozzle capacity and is being returned to the tank (twin-pipe system) or being returned to the suction pipe through a bypass in the pipe (sin- gle-pipe system).
  • Page 27: Suntec At2 Pump

    SUNTEC AT2 PUMP The SUNTEC AT2 oil pump features 2 mode pressure operation and incorporates a blocking solenoid valve with in-line cut-off function. Switching between low and high modes is assured by a 2nd integral solenoid valve. Operation The gear set draws oil from the tank through the built-in filter and transfers it to the nozzle line via the cut-off solenoid valve. Pressure regulation is assured by two spool valves, one for each pressure mode.
  • Page 28: Notes For Use And Maintenance Of Fuel Pumps

    NOTES FOR USE AND MAINTENANCE OF FUEL PUMPS Make sure that the by-pass plug is not used in a single pipe installation, because the fuel unit will not function properly and damage to the pump and burner motor could result. Do not use fuel with additives to avoid the possible formation over time of compounds which may deposit between the gear teeth, thus obstructing them.
  • Page 29 APPENDICX: COMPONENTS CHARACTERISTICS...
  • Page 30 APPENDICX: COMPONENTS CHARACTERISTICS...
  • Page 31 APPENDICX: COMPONENTS CHARACTERISTICS...