RWF55 is preset good for 90% of applications. However, you can set or edit parameters as follow:
Set-point: set or modification:
When the burner is in stand-by, (safety loop open, that is terminals 3-4/T1-T2 on the 7 pole plug open) push the Enter button: on the lower display
(green) Opr appears; push Enter again and in the same display SP1 appears. Push Enter again and the lower display (green SP1) flashes. Using the up
and down arrows change the set-point on the upper display (red).Push Enter to confirm and push ESC more times to get the home position.
next parameter
one level
down
previous parameter
Parameter level
4
User Level - Opr
SP1 or SP2 (editable)
dSP readable and editable
through bin1 = 2
InP1 or y (only display)
Parameter level - PArA
Pb1, dt, rt, db, tt
Heating controllerHYS1 , HYS2 ,
HYS3
Cooling controller
HYS4 , HYS5 , HYS6
q, At1, Ht1, At2, Ht2
Configuration level – ConF
and lower level
Analog inputs
Controller
Thermal shock protection
Alarm function
Controllig outputs
Binary inputs
Display
Interface
InP ..
Cntr
rAFC
AF
outP
binF
diSP
intF