Unigas PBY1025 Manual Of Installation - Use - Maintenance page 10

Progressive, fully-modulating heavy oil burners
Table of Contents

Advertisement

PBY1030 - PBY1040
PI
PI
M
PS
M
combustion air
M
PSL
PI
LPG gas - out of Cib Unigas scope of supply
The following items are out of CIB UNIGAS scope of supply: 77 - 78 - 79
Fig. 3 - (3I2D-03 v5) Hydraulic diagram
PI
PS
PI
PI
TS
TSL
TSH
TC
TC
TC
ON BOARD ITEMS
SUPPLIED LOOSE ITEMS
compressed air
M
oil inlet
to the tank
natural gas / LPG
BY OTHERS
BY BURNER CONSTRUCTOR
LEGEND
POS OIL TRAIN
1
Filter
2
Pump with electromotor
3
Flexible hose
4
Maual valve
5
Pressure gauge
6
Pressure governor
7
Maual valve
8
Thermostat
9
Low thermostat
10 High thermostat
11 Electrical preheater tank
12 Temperature probe
13 Temperature probe
14 Temperature probe
16 Pneumatic valve
17 Metering valve with servomotor
18 Actuator
19 Maual valve
20 Pressure gauge
21 Flexible hose
COMPRESSED AIR TRAIN (ATOMIZATION)
40 Pressure governor with filter
41 Pressure gauge
42 Solenoid valve
43 Pressure switch
44 One-way valve
45 Metering valve
46 Manual valve
47 Pressure gauge
48 Flexible hose
COMPRESSED AIR TRAIN (PURGE)
50 Pressure governor with filter
51 Pressure gauge
52 Solenoid valve
53 One-way valve
PILOT GAS TRAIN
71 Pressure governor with filter
72 Pressure switch
73 Solenoid valve
74 Flexible hose
75 Pilot burner
76 Pressure governor for L.P.G. tank
77 Manual valve
78 Pressure gauge
79 L.P.G. tank
COMBUSTION AIR TRAIN
80 Air damper
81 Actuator
82 Remote draught fan with electromotor
83 Pressure switch - PA
86 Burner

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pby1030Pby1040