Unigas PBY1025 Manual Of Installation - Use - Maintenance page 20

Progressive, fully-modulating heavy oil burners
Table of Contents

Advertisement

Light oil pilot
The burner can be provided with light oil pilot, instead of gas pilot.
light oil pilot nozzle
Key
EVG Light oil solenoid valve
M
Manometer
P
Pump
Heavy oil pumps
The pump provided with the burner must be installed according to the hydraulic diagram.
Cucchi FMG40 pumps
Capacity: 2500l/h
Power consumption: 1.1 kW
Speed: 1400 rpm
Max outlet pressure: 10bar
Max inlet pressure: 2bar
Min inlet pressure: -0.4bar
For further details see the manifacturer documentation.
Suntec TV Pressure governor
Pressure adjustment
Remove cap-nut 1 and the gasket 2, unscrew the lock nut 4. To increase pressure,
twist adjusting screw 3 clockwise.
To decrease the pressure, twist screw counterclockwise. Tight the lock nut 4, refit the
gasket 2 and the cap nut 1.
Key
1
Cap nut
2
Gasket
3
Adjusting screw
4
Lock nut
5
Gasket
C.I.B. UNIGAS - M039126CE
light oil pilot pump
P
M
20
Fig. 17
EVG
Fig. 18