Installation

Burner installation

The surface of the
Seal corners with
entire circumference
sealing tape
must be sealed
Burner flange seal (option 1)
The sealing tape in the accessories kit
must be affixed to the burner as shown
in the drawing below. The sealing tape
should be affixed without gaps in order
to prevent exhaust from escaping during
burner operation.
Please note:
Depending on the fibre diameter, the
mineral fibre sealing thermocord may
cause reversible mechanical irritation to
the eyes and skin. In the event of high
dust concentrations, risk of mechanical
irritation to upper respiratory tract.
When working with the sealing
Burner flange seal (option 2)
• Check whether the gasket 1 is fitted
and in the correct position.
• Remove KB fixing clamps prior to
installation.
03/2016 - Art. Nr. 4200 1044 8002A
thermocord, the operator should wear
loose-fitting, long-sleeved clothing. In
the event of high fibre dust
concentrations, the operator should
wear an FFP1 mask and well-sealed
protective goggles (also when carrying
out overhead work).
Burner installation
• Attach boiler front gasket to the burner
(see section entitled Burner front
gasket)
• Lift burner using hoisting eyes 19 (see
page 4 N6/7/8/9, see page 5 EKEVO
6/7/8/9) and fasten to the boiler.*
• Tighten the 4 fastening screws S2
(check the tightening torques).
* Alternatively a forklift truck may be
used for fixing it if the burner is fixed
to the transport pallet supplied with it.
Provision must be made for adequate
transportation safety. Suitable
transportation materials must be
used if necessary (lashing straps).
The leaktightness of the connection
between the burner and the boiler must
be tested during operation. It must be
ensured that exhaust cannot escape in
harmful quantities. Poorly sealed burner
boiler connections may result in
combustion problems.