Commissioning

Burner control unit

Description
The electronic burner controller is a
programmable automatic firing device
with an integrated electronic compound
controller. There may be additional
functions, depending on the equipment
and model.
The following burner-specific controllers
are used:
Burner controller
Manufacturer
Technical data
Operation mode
Components and integrated
functions
optional equipment
Additionally, some burners are delivered
without a controller and all components
are connected to a terminal block. The
burner controller in this case does not
form part of the burner's scope of
delivery.
Burners equipped with the BT3xx control
unit are controlled and regulated using a
manual terminal (display) or PC
software. The user instructions for the
display and the PC are included in the
additional operating instructions for the
BT3xx:
Save the data after starting the burner
and after changing any data in the
Burnertronic control unit (e.g. changed
curves or parameters.) To this end
backup all the data. The relevant
procedure is described in the operating
instructions "BurnerTronic BT300 -
Remote Software, Maintenance" (Art.
No. 4200 1017 5301) under chapters
"Files" and "Data Saving". This will allow
44
BT 340
Lamtec
Operating voltage: 230 VAC
Frequency: 50/60 Hz
Power consumption: approx. 30 VA
Ambient temperature:
during operation: -20 to +-60°C
Storage: -25 to +60°C
3 outputs for motorised actuators (1x 0...10V
permanent, 0/4...20mA)
Intermittent/continuous operation
Servomotor STE 4.5
Customer interface
integrated valve leak check
Programming unit
Speed control extension module
Extension module LCM 100
O
/CO regulation
2
Connection of a field bus (via the optional LCM100
module):
- PROFIBUS
- Modbus
- Ethernet (Modbus TCP)
- 420010485601 Description of the unit,
display, settings
- 420010175301 Remote software
- 420010xxxxxx CO/O2 regulation
- 420010178501 List of fault codes
- 420010181501 List of parameters
Commissioning
Commissioning must be carried out by
trained and expert personnel only. For
the wiring of the system, the relevant
electrical diagram for the burner and all
local standards and legal regulations
must be observed.
the burner to restart easily and quickly
after replacing the Burnertronic control
unit.
03/2016 - Art. Nr. 4200 1044 8002A
The procedure described in the relevant
operating instructions for the burner
controller must be observed. The burner
controller has a burner-specific factory
setting. At the time of initial
commissioning, it must be checked
whether the parameters have been
appropriately configured to meet the
requirements of the system. The
servomotors must similarly be checked
for correct adjustment.
During the I/O test, the manual gas shut-
off valves must be kept closed at all
times. It is not permitted to extend fixed
safety times using external circuitry.