05: ECO mode enable/disable
06: Voltage range for ECO mode
07: Frequency range for ECO mode
28
Parameter 3:
Enable or disable ECO function.
Available options:
DIS:
disable ECO function
ENA:
enable ECO function
If ECO function is disabled, voltage range and
frequency range for ECO mode still can be set,
but it is meaningless unless the ECO function
is enabled.
Parameter 2:
Low voltage point in ECO mode.
The setting range is from 5% to 10% of the
nominal voltage.
Parameter 3:
High voltage point in ECO mode.
The setting range is from 5% to 10% of the
nominal voltage.
Parameter 2:
Set low frequency point for ECO
mode.
50 Hz system: Setting range is from 46.0Hz
to 48.0Hz.
60 Hz system: Setting range is from 56.0Hz
to 58.0Hz.
The default value is 48.0Hz/58.0Hz.
Parameter 3:
Set high frequency point for
ECO mode.
50 Hz: Setting range is from 52.0Hz to 54.0
Hz.
60 Hz: Setting range is from 62.0Hz to
64.0Hz.
The default value is 52.0Hz/62.0Hz.