Njoy Balder Series User Manual page 26

Hide thumbs Also See for Balder Series:
Table of Contents

Advertisement

Available languages

Available languages

Interface
01: Output voltage settings
0 1
2 2 0
O U T P U T
NOTE!
When the output voltage is set to 208V, the power of the UPS is de-rated to 90%.
02: Output frequency
60 Hz, CVCF mode
02
6 0 0
Hz
O U T P U T
50 Hz, Normal mode
02
5 0 0 N C
Hz
O U T P U T
ATO
02
F
A 0
5 0 0
O U T P U T
26
Settings
Parameter 3:
You may choose the following output voltage
in parameter 3:
Vac
208:
220:
230:
240:
Parameter 2:
Setting the output frequency as follows:
50.0Hz:
f
C
50.0Hz.
60.0Hz:
60.0Hz.
ATO:
decided according to the latest normal utility
frequency. If it is from 46Hz to 54Hz, the
output frequency will be 50.0Hz. If it is from
f
56Hz to 64Hz, the output frequency will be
60.0Hz. ATO is default setting.
Parameter 3:
Setting output frequency at CVCF mode or
not CVCF mode. You may choose following
two options in parameter 3:
CF:
the output frequency will be fixed at 50Hz or
Hz
60Hz according to setting in parameter 2. The
input frequency could be from 46Hz to 64Hz.
Output voltage
presets output voltage is 208Vac
presets output voltage is 220Vac
presets output voltage is 230Vac
presets output voltage is 240Vac
Output Frequency
The output frequency is setting for
The output frequency is setting for
If selected, output frequency will be
Frequency mode
Setting UPS to CVCF mode. If selected,